Transducer should not be subjected to greater than the maximum allowable pressure or  

temperature as defined in the transducer specification. 

Transducer should not be subjected to mechanical impact. 

In the event of fire the end user must ensure that the system pressure is vented to a safe  

area. 

The effects of decomposition of unstable fluids should be considered by the user when  

placing this device in service. 

The pressure transducer has no means of draining or venting, this must be performed by  

another component in the end users system. 

Pressure range must be compatible with the maximum pressure being measured. 

Pressure media must be compatible with the transducer wetted parts which are stainless 

steel to UNS 31803, Ceramic and Nitrile

 

 

 

Exposed end of cable must be kept free from moisture. 

Liquid must not be allowed to freeze in the pressure port. 

Full specifications for all products available on request from our Service Department. 

 

MECHANICAL INSTALLATION

 

 

Pressure Connections:   

 

1) 

G¼  internal  pressure  connection  to  BS2779.    Alternative  fitted  as  specified  at  time  of 

order. 

 

2)

 

KF25 Flange 

 

Pressure couplings screwed into G¼ pressure ports should have a maximum thread engagement 

of  13  mm  and 

UNDER  NO  CIRCUMSTANCES  be  allowed  to  touch  the  pressure  sensitive 

diaphragm.  Pressure couplings should be sealed against the outer face at the pressure port entry 

using bonded seal washer such as:- 

 

Part Number  

 

Description 

 

234646-0002   

 

G¼ bonded seal up to +100°C operation. 

 

 

 

 

 

Dowty Ref: 400-021-4490-02 

 

499207-0002   

 

G¼ bonded seal up to +200°C operation. 

 

 

 

 

 

Dowty Ref:  300-021-0967-02 

 

 

499207-0006   

 

G1/8 bonded seal up to +200°C operation. 

 

 

 

 

 

Dowty Ref:  300-020-0967-02 

 

Refer to Dowty for external pressure ratings. 

 

Mounting: Pressure Transducer is designed to be attached by the coupling thread.  Alternatively 

units fitted with an immersible cable can be suspended via the cable or flange.  Omni-directional.  

To fit, use a M16 (5/8 UNF) AF spanner on the hexagon provided and apply maximum torque of 

27 Nm (20 lbf-ft). The Customer must ensure that the pressure seal is suitable for the application.   

 

Summary of Contents for 5000 series

Page 1: ...e requirements of the CE mark only applies when the installation conditions described in these instructions have been met For units supplied without a cable assembly connection to the transducer must be accomplished using approved cable see APPROVED CABLE section All instruments conform to the appropriate specifications and or drawings applicable and have been subjected to relevant strict quality ...

Page 2: ... Department MECHANICAL INSTALLATION Pressure Connections 1 G internal pressure connection to BS2779 Alternative fitted as specified at time of order 2 KF25 Flange Pressure couplings screwed into G pressure ports should have a maximum thread engagement of 13 mm and UNDER NO CIRCUMSTANCES be allowed to touch the pressure sensitive diaphragm Pressure couplings should be sealed against the outer face ...

Page 3: ...ive outer sheath materials available on request for harsh environments OPERATION Having installed the transducers as instructed they are ready for use The transducer should not be removed whilst the system is at pressure Before applying power check that the correct polarity and excitation levels are being applied See ELECTRICAL REQUIREMENTS Cable Version 20 C to 50 C Connector Version 25 C to 85 C...

Page 4: ... Not Used A Y 3 Not Used B Z 4 W C Not Used 5 X D Not Used 6 Y E Not Used 7 Z F Not Used Range Downranging Scope Nominal W 110 to 74 X 78 to 52 Y 54 to 37 Z 47 to 32 LOAD RESISTANCE 4 20mA Transmitter The total permissible resistive load in the loop to include all the cable resistance can be from zero to 50 x supply volts 8 5 ohms e g with a 12V d c supply the permissible load is from zero up to 1...

Page 5: ...nal part Modification misuse attempted repair by others improper installation or operation shall render this guarantee null and void The Company makes no warranty of merchantability or fitness for a part or purpose SERVICING The transducer cannot be repaired locally and if damaged should be returned to ourselves at the address shown below Pulsar Process Measurement Limited Oak House Bromyard Road ...

Page 6: ...ERVICE DEPARTMENT TO ASCERTAIN IF THE INSTRUMENT CONTAINS VITON W A R N I N G ELECTRICAL CONNECTIONS 4 20MA VOLTAGE IN IN EARTH IN COM OUT EARTH CABLE R BL DRAIN R W Y DRAIN CONNECTOR 1 2 E 1 2 3 E OUTPUT SUPPLY VOLTAGE 4 20mA 9 35V d c 0 5 5 5V d c 7 5 35V d c 1 6V d c 8 35V d c 0 5V d c 7 5 35V d c 0 1 5 1V d c 7 5 35V d c 1 5V d c 7 5 35V d c ...