background image

 

 

QS3.241 

 

 

 

 

Q-Series 

24V,

 

3.4A,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

Jul. 2020 / Rev. 2.3 DS-QS3.241-EN 

All parameters are specified at 24V, 3.4A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

3/26 

 

1.

 

I

NTENDED 

U

SE

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, 

process control, monitoring and measurement equipment or the like.  

Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without 

additional appropriate safety devices, that are suited for the end-application.  

If this device is used in a manner outside of its specification, the protection provided by the device may be impaired. 

 

2.

 

I

NSTALLATION 

R

EQUIREMENTS

 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. Install the device onto a 

DIN-rail according to EN 60715 with the input terminals on the bottom of the device. Other mounting orientations require a 

reduction in output current.  

Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are 

designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient 

temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire enter 

the terminal connection. Use ferrules for wires on the input terminals.  

The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.  

The enclosure of the device provides a degree of protection of IP20. The housing does not provide protection against spilled 

liquids.  

The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested for impulse withstand 

voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1.  

The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use without a proper PE 

(Protective Earth) connection.  

The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage between the input terminal 

and the PE potential must not exceed 276Vac.  

The input can also be powered from batteries or similar DC sources. The continuous voltage between the supply voltage and 

the PE/ground potential must not exceed 375Vdc.  

A disconnecting means shall be provided for the input of the device.  

The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover 

ventilation grid!  

The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in output current is required. 

Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase 

the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, 

the 5mm can be reduced to zero. 

 The device is designed, tested and approved for branch circuits up to 20A without additional protection device. If an external 

fuse is utilized, do not use circuit breakers smaller than 6A B- or 4A C-Characteristic to avoid a nuisance tripping of the circuit 

breaker.  

The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or 

surrounding air temperature and is defined 2cm below the device. The device is designed to operate in areas between 5% 

and 95% relative humidity. 

 

WARNING

  Risk of electrical shock, fire, personal injury or death. 

-  Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth 

connection and not one of the screws on the housing. 

-  Turn power off before working on the device. Protect against inadvertent re-powering. 

-  Make sure that the wiring is correct by following all local and national codes. 

-  Do not modify or repair the unit. 

-  Do not open the unit as high voltages are present inside. 

-  Use caution to prevent any foreign objects from entering the housing. 

-  Do not use in wet locations or in areas where moisture or condensation can be expected. 

-  Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns. 

 

Notes for use in hazardous location areas: 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations. 

WARNING EXPLOSION HAZARDS!  

Substitution of components may impair suitability for this environment.  

Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is known to 

be non-hazardous. 

Summary of Contents for YR20.242

Page 1: ...ss to be used High immunity to transients and power surges as well as low electromagnetic emission makes usage in nearly every environment possible The integrated output power manager a wide range inp...

Page 2: ...22 13 Mounting Orientations 26 The information given in this document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwise this informat...

Page 3: ...tential must not exceed 276Vac The input can also be powered from batteries or similar DC sources The continuous voltage between the supply voltage and the PE ground potential must not exceed 375Vdc A...

Page 4: ...ig 3 4 Crest factor typ 3 33 3 9 3 88 at 24V 3 4A Start up delay typ 360ms 350ms 330ms see Fig 3 2 Rise time typ 6ms 5ms 7ms 0mF 24V 3 4A see Fig 3 2 typ 20ms 20ms 22ms 3 4mF 24V 3 4A see Fig 3 2 Turn...

Page 5: ...source For other sources contact PULS b Connect pole to L and pole to N c Connect the PE terminal to a earth wire or to the machine ground 5 INPUT INRUSH CURRENT An active inrush limitation circuit l...

Page 6: ...Power load impedance 25mOhm max 6 0A continuous load impedance 10mOhm see Fig 6 1 Output capacitance typ 1 500 F included inside the power supply BonusPower short term power capability up to typ 4s Th...

Page 7: ...t e rm Adjustment Range con tin uou s Bonus Time 0 110 120 130 140 150 160 1 2 3 7 4 5 6 8 9 10s min max typ Output Power Fig 6 3 BonusPower recovery time Power Demand 100 t t Limitation by Power Man...

Page 8: ...0 Germany 8 26 7 HOLD UP TIME AC 100V AC 120V AC 230V Hold up Time typ 58ms 88ms 347ms at 24V 1 7A see Fig 7 1 typ 28ms 41ms 174ms at 24V 3 4A see Fig 7 1 Fig 7 1 Hold up time vs input voltage Fig 7 2...

Page 9: ...here the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the n...

Page 10: ...ife and is determined by the lifetime expectancy of the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufactur...

Page 11: ...pring clamp terminals Solid wire 0 5 6mm2 0 3 4mm2 Stranded wire 0 5 4mm2 0 3 2 5mm2 American Wire Gauge 20 10 AWG 26 12 AWG Wire stripping length 10mm 0 4inch 6mm 0 25inch Screwdriver not applicable...

Page 12: ...tive output Negative return output C Output voltage potentiometer Multi turn potentiometer Open the flap to adjust the output voltage Factory set 24 1V D DC OK LED green On when the output voltage is...

Page 13: ...40Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0 of 200Vac 0V 5000ms Criterion C Voltage sags SEMI F47 0706 dips on the input v...

Page 14: ...560ft without any restrictions 2000 to 6000m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 14 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 5W 1000m or 5 C 100...

Page 15: ...nt leakage current typ 0 11mA 0 26mA 100Vac 50Hz TN TT mains IT mains typ 0 15mA 0 38mA 120Vac 60Hz TN TT mains IT mains typ 0 25mA 0 63mA 230Vac 50Hz TN TT mains IT mains 0 14mA 0 31mA 110Vac 50Hz TN...

Page 16: ...icate TAA00002JT Temperature Class D Humidity Class B Vibration Class C EMC Class A Enclosure Class A Marine ABS Design Assessment Certificate ABS American Bureau of Shipment assessed product Certific...

Page 17: ...irective LVD RoHS directive REACH Directive Manufacturer s Statement EU Directive regarding the Registration Evaluation Authorisation and Restriction of Chemicals EAC TR Registration Registration for...

Page 18: ...noted www pulspower com Phone 49 89 9278 0 Germany 18 26 20 PHYSICAL DIMENSIONS AND WEIGHT Weight 440g 0 97lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15m...

Page 19: ...e power supply onto a flat surface without utilizing a DIN Rail 21 2 ZM11 SIDE SIDE MOUNTING BRACKET This bracket is used to mount Dimension units sideways with or without utilizing a DIN Rail The two...

Page 20: ...al current The buffer unit does not require any control wiring It can be added in parallel to the load circuit at any given point Buffer units can be added in parallel to increase the output ampacity...

Page 21: ...e unit will respond with a thermal shut down after a period of time Use the maximum duty cycle curve Fig 23 2 to check if the average output current is below the nominal current Fig 23 1 Repetitive pu...

Page 22: ...ltage dips Fig 23 3 Peak load with 2x the nominal current for 50ms typ Fig 23 4 Peak load with 4x the nominal current for 5ms typ Peak load 6 8A resistive for 50ms Output voltage dips from 24V to 18 5...

Page 23: ...or redundancy module can also be utilized Keep an installation clearance of 15mm left right between two power supplies and avoid installing the power supplies on top of each other Do not use power su...

Page 24: ...terminals Power Supply Input Output Load max 13A Power Supply Input Output Load Distribution Terminals Power Supply Input Output Power Supply Input Output 22 9 SERIES OPERATION Power supplies of the...

Page 25: ...put Protection 22 12 USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure the temperature inside the enclosure will be higher than outside In such situati...

Page 26: ...t Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 23 7 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Current 0 10 20...

Reviews: