DC UPS Instruction Manual  
Bedienungsanleitung für die DC USV UB20.241 
 

 

 

Product Description 

The UB20.241 offers a DIN-rail DC-UPS which bridges power outages of the 24Vdc-supply. The 
UB20.241 can be used with batteries up to 130Ah to offer longer buffer-times. The unit uses two 
12V batteries in series. It is possible to charge and monitor each battery separately if the centre 
point of the batteries is connected with the DC-UPS. Additionally the UB20.241 has a lot of 
diagnosis- and monitoring functions included. The output voltage in buffer mode is constant and 
can be set to four different values. This behavior offers new possibilities for buffered 24V DC 
applications with long wires. 
In combination with PULS intelligent battery modules the refresh function of the UB20.241 can be 
used. This allows the “reanimation” of deep discharged batteries. 

 

Gerätebeschreibung 

Das UB20.241 dient zur Überbrückung von Netzausfällen der geregelten 24V DC-Versorgung. 
Zur Realisierung besonders langer Überbrückungszeiten kann das UB20.241 mit Batterien bis 
zu 130Ah Stunden eingesetzt werden. Als Energiespeicher werden zwei 12V Batterien in Serie 
verwendet. Durch Anschluss des Batteriemittelpunkts kann jede Batterie getrennt überwacht 
und geladen werden. Zusätzlich verfügt das UB20.241 über umfangreiche Melde und 
Überwachungsfunktionen. Auch im Pufferbetrieb ist die Ausgangsspannung konstant und lässt 
sich auf vier verschiedenen Stufen einstellen. Dadurch ergeben sich für gepufferte 24V DC 
Anwendungen mit langen Leitungen neue Möglichkeiten. 
In Verbindung mit den intelligenten PULS Batteriemodulen kann die Refresh Funktion genutzt 
werden. Hierdurch können tiefentladene Batterien „reanimiert“ werden.  

 

Technical Data 

1)

 Technische 

Daten 

1)

 

UB20.241 

Output Voltage  

Ausgangsspannung  

nom.

24V

2)

 

Output Current normal Mode

 continues

 Ausgangsstrom 

Normalbetrieb 

dauernd

 

nom.

25A

3)

 

Output Current Buffer Mode

 continues

 Ausgangsstrom 

Pufferbetrieb 

dauernd

 

nom.

20A

4)

 

Output Current Buffer Mode

 for typical 4s

 Ausgangsstrom 

Pufferbetrieb

 für typisch 4s

 

nom.

30A 

Output Power Normal Mode 

Ausgangsleistung Normalbetrieb 

720W 

Output Power Buffer Mode 

continues

 Ausgangsleistung 

Pufferbetrieb

 dauernd

 

450W 

Output Power Buffer Mode 

for typical 4s

 Ausgangsleistung 

Pufferbetrieb 

für typisch 4s

 

675W 

Input Voltage 

Eingangsspannung 

DC 24V 

Input Voltage Range 

Eingangsspannungsbereich 

23.3 – 30Vdc 

Turn on voltage

5)

 Einschaltschwelle

5)

 

typ.

23.3Vdc 

Transfer Threshold Buffer Mode

6)

 Umschaltschwelle 

Pufferbetrieb

6)

 

variable 

Allowed Batteries 

Erlaubte Batterien 

12V, VRLA

7)

 

Allowed Battery Capacity 

Erlaubte Batteriekapazität 

3.9Ah – 130Ah 

Power Losses 

Verlustleistung 

typ.

3.7W 

8)

 

Operational Temperature 

Betriebstemperatur 

      

-40 - +70°C

9)

 

Storage Temp. Range 

Lagertemperaturbereich 

-40 - +85°C 

Humidity Feuchte 

IEC60068-2-30

5 – 95% r.H. 

10)

 

Vibration Schwingen 

IEC 60068-2-6

2g 

Shock Schock 

IEC60068-2-27

30g 6ms, 20g 11ms 

Degree of Pollution 

Verschmutzungsgrad 

EN 50178

Degree of Protection 

Schutzart 

EN 60529

IP20 

Over-temp. Protection 

Übertemperaturschutz 

Yes / Ja 

11)

 

Parallel Use 

Parallelschaltbar 

No / Nein 

Serial Use 

Serienschaltbar 

No / Nein 

Dimensions 

(wxhxd)

 Abmessungen 

(BxHxT)

 

nom.

46x124x127mm 

12)

 

Weight Gewicht 

max.

750g / 1.65lb 

Approvals Zulassungen 

 

13)

 

Limited Warranty 

(Year)

 Gewährleistung

 (Jahre)

 

1)  All parameters are specified at 24Vdc input voltage, nominal output current, 25°C ambient and 

after a 5 minutes run-in time unless otherwise noted. 

2)  In normal mode, the output voltage is max. 0.15V lower than the input voltage assuming that the 

input voltage is sufficient and no overload is present. The output voltage is regulated to the 
adjusted value in a buffer event. 

3)  It is necessary to use a fuse on the input of the DC-UPS if the output current of the supplying 

source is higher than 28A. 

4)  At 22.5V Buffer-voltage, at higher voltage a derating is required (24V->19.5A, 25V->18.5A, 26V-

>18A) 

5)  This value must be passed one time for the DC-UPS to start 
6)  Similar to the selected buffer-voltage. 
7)  Two batteries have to be connected in series 
8)  Battery is fully charged. At 20A load, no buffer event is present. 
9)  Derating above +60°C 0.5A/°C 
10) Do not energize while condensation is present. 
11) Output shuts down with automatic restart after cooling down in buffer mode. 
12) Depth without DIN-rail. 
13) See datasheet or markings on the unit. 

1)  Alle Werte gelten bei 24Vdc Eingangsspannung, 25°C Umgebung und nach einer Aufwärmzeit von 

5 Minuten, wenn nichts anderes angegeben ist. 

2)  Im Normalbetrieb ist die Ausgangsspannung max. 0.15V kleiner als die Eingangsspannung, 

vorausgesetzt dass die Eingangsspannung im spezifizierten Bereich ist und keine Überlast vorliegt. 
Währen eines Pufferfalls ist die Ausgangsspannung auf den eingestellten Wert geregelt. 

3)  Bei Einsatz einer Stromversorgung mit mehr als 28A Ausgangsstrom ist eine Sicherung am 

Eingang der USV vorzusehen. 

4)  Bei 22.5V Pufferspannung, bei höheren Spannungen ist ein Derating vorzunehmen (24V->19.5A, 

25V->18.5A, 26V->18A) 

5)  Dieser Wert muss einmalig überschritten werden, damit die DC-USV anläuft. 
6)  Entspricht der eingestellten Pufferspannung  
7)  Es müssen zwei Batterien in Serie geschalten werden 
8)  Gilt bei: Voll geladenen Batterien; 20A Last kein Pufferbetrieb.  
9)  Ab +60°C gilt ein Derating von 0.5A/°C 
10) Nicht betreiben, solange das Gerät Kondensat aufweist 
11) Im Pufferbetrieb schaltet der Ausgang ab und startet nach Abkühlung automatisch.  
12) Tiefe ohne DIN-Schiene 
13) Siehe Datenblätter oder Prüfzeichen auf dem Gerät 