background image

 

 

 

ML15.121 

 

MiniLine

 

 

12V, 1.3A, S

INGLE 

P

HASE 

I

NPUT

 

 

 

Dec. 2007 / Rev. 1.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

13/20 

 

20. A

PPROVALS

 

 

 IEC 

60950-1 

IECEE

 

CB SCHEME

 

CB Scheme,  
Information Technology Equipment 

 UL 

508 

IND. CONT. EQ.

18WM

LISTED

 

LISTED E198865 
Industrial Control Equipment

 

 UL 

60950-1 

 

RECOGNIZED   E137006   recognized for the use in U.S.A. (UL 60950-1) and Canada 
(C22.2 No. 60950).  Information Technology Equipment, Level 3  

  NEC Class 2 

 

According to NEC (National Electrical Code) Article 725-41 (4). 
Listed as Limited Power Source (LPS) in the UL 60950-1 UL report. 

 

Class I Div 2 
 

 

RECOGNIZED   E246877    
Hazardous Location Class I Div 2 T4 Groups A,B,C and D  
ANSI/ISA-12.12.01 (UL 1604) 

   

The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations. Substitution of components 
may impair suitability for Class I Division 2 environment. Do not disconnect equipment unless power has 
been switched off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National 
Electrical Code, NFPA 70, and in accordance with other local or national codes. 

  CSA 

 

R

182790

C

US

 

CSA approval for Canada 
CAN/CSA C22.2 No 107-1; CAN/ CSA 60950-1-03; UL60950-1 

 Marine 

 

GL

  

ABS

 

GL (Germanischer Lloyd) classified and ABS (American Bureau for Shipping) PDA 
for marine and offshore applications. Environmental category: C, EMC2 

 

 

21. F

ULFILLED 

S

TANDARDS

 

 

  EN 61558-2-17 

Safety of Power Transformers 

  EN/IEC 60204-1 

Safety of Electrical Equipment of Machines 

  EN/IEC 61131-2 

Programmable Controllers 

  EN 50178, IEC 62103 

Electronic Equipment in Power Installations 

 
 

22. U

SED 

S

UBSTANCES

 

 

  Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems. 

  The unit conforms to the RoHS directive 2002/96/EC 

  Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated. 

 

The materials used in our production process do not include the following toxic chemicals: 
Polychlorinated Biphenyl (PCB), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrominated  
Biphenyl (PBB), Polybrominated Biphenyl Oxide (PBO), Polybrominated Diphenyl Ether (PBDE), Polychlorinated 
Diphenyl Ether (PCDE), Polybrominated Diphenyl Oxide (PBDO), Cadmium, Asbestos, Mercury, Silica 

Summary of Contents for MiniLine ML15.121

Page 1: ...230Vac Temperature range 10 C to 70 C Operational Derating 0 4W C 60 to 70 C Hold up time typ 46 191ms At 120 230Vac Dimensions 22 5x75x91mm WxHxD A compact size light weight simple mounting onto the...

Page 2: ...pply shall only be installed and put into operation by qualified personnel This power supply is designed for installation in an enclosure and is intended for the general use such as in industrial cont...

Page 3: ...t 12V 1 3A Start up delay typ 780ms 780ms 780ms See Fig 5 2 Rise time typ 12ms 12ms 12ms At 12V 1 3A see Fig 5 2 Turn on overshoot max 100mV 100mV 100mV See Fig 5 2 The power factor is the ratio of th...

Page 4: ...the first peak Input Voltage Input Current Input Current Input 230Vac Output 12V 1 3A Ambient 25 C Upper curve Input current 5A DIV Lower curve Input voltage 500V DIV Time scale 10ms DIV Input 230Vac...

Page 5: ...ange min 85 375Vdc Continuous operation DC input current typ 0 16A 0 057A 110Vdc 300Vdc at a load of 12V and 1 3A Turn on voltage typ 80Vdc Steady state value Shut down voltage typ 60Vdc Steady state...

Page 6: ...mode See Fig 9 2 max Hiccup mode See Fig 9 2 Fig 9 1 Output voltage vs output current typ Fig 9 2 Hiccup mode Output current at shorted output 230V typ Output Voltage 0 0 2 4 6 16V 8 10 12 2 0A 1 0 0...

Page 7: ...f load typ 3 4W 3 2W 3 1W 1 3A 12V full load Fig 10 1 Efficiency vs output current at 12V Fig 10 2 Losses vs output current at 12V Efficiency 0 2 77 78 79 80 81 82 83 76 84 1 4A 0 6 0 8 1 2 Output Cur...

Page 8: ...ars 15 years 15 years 25 C 12V 1 3A MTBF SN 29500 IEC 61709 3 435 000h 3 723 000h 3 811 000h 40 C 12V 1 3A 5 633 000h 6 106 000h 6 205 000h 25 C 12V 1 3A MTBF MIL HDBK 217F 1 482 000h 1 534 000h 1 451...

Page 9: ...er Turn to set the output voltage Factory setting is 12 0V 14 TERMINALS AND WIRING All terminals are easy to access when mounted on the panel Input and output terminals are separated from each other i...

Page 10: ...of 100Vac 40 of 100Vac 70 of 100Vac 0 of 200Vac 40 of 200Vac 70 of 200Vac 0Vac 20ms 40Vac 200ms 70Vac 500ms 0Vac 20ms 80Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion...

Page 11: ...6000m Degree of pollution 2 EN 50178 IEC 62103 non conductive Fig 16 1 Output power vs ambient temperature Fig 16 2 Output power vs altitude 0 10 0 20 40 70 C 2 5 5 0 7 5 10 0 12 5 15W 60 Ambient Temp...

Page 12: ...terminal connected to Protective earth 2 Functional earth terminal not connected 19 DIELECTRIC STRENGTH Fig 19 1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac...

Page 13: ...Division 2 wiring methods of the National Electrical Code NFPA 70 and in accordance with other local or national codes CSA R 182790 C US CSA approval for Canada CAN CSA C22 2 No 107 1 CAN CSA 60950 1...

Page 14: ...see chapter 25 12 An appropriate electrical and fire end product enclosure should be considered in the end use application Cooling Convection cooled no forced cooling required Do not cover ventilation...

Page 15: ...dips Fig 25 1 Peak load 2 6A for 50ms typ Fig 25 2 Peak load 6 5A for 5ms typ 10ms DIV Output Voltage Output Current 12V 0A 2 6A 7 8V 1ms DIV Output Voltage Output Current 12V 0A 6 5A 2V Peak load 2...

Page 16: ...quired when the sum of the output voltage is above 60Vdc Note Avoid return voltage e g from a decelerating motor or battery which is applied to the output terminals 25 5 PARALLEL USE TO INCREASE OUTPU...

Page 17: ...ing module MLY02 100 Other recommendations for building redundant power systems a Use separate input fuses for each power supply b Set the output voltage of the power supplies approx 1V higher to comp...

Page 18: ...side caused by the input are much smaller compared to not connecting the FE terminal to ground Therefore we recommend to connect the FE terminal too ground Fig 25 5 Functional earth terminal connected...

Page 19: ...mperature for the power supply Results from such an installation Power supply is placed in the middle of the box no other heat producing equipment inside the box Enclosure Rittal Type IP66 Box PK 9510...

Page 20: ...ve A1 Recommended output power Curve A2 Max allowed output power results approx in half the lifetime expectancy of A1 Fig 25 8 Mounting Orientation A Standard Orientation Power Supply OUTPUT INPUT Out...

Reviews: