ML15.121 

 

MiniLine

 

 

12V, 1.3A, S

INGLE 

P

HASE 

I

NPUT

 

 

 

Dec. 2007 / Rev. 1.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

10/20 

 

15. EMC 

 

The CE mark indicates conformance with EMC directive 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage 
directive (LVD) 73/23/EC, 93/68/EC, 2006/95/EC. A detailed EMC Report is available on request. 

All results and investigation were performed with functional earth wire. 

 

 

EMC Immunity 

EN 61000-6-2, EN 61000-6-1   

Generic standards 

 

Electrostatic discharge  

EN 61000-4-2 

Contact discharge 
Air discharge 

8kV 
8kV 

Criterion A 
Criterion A 

  Electromagnetic RF field 

EN 61000-4-3 80MHz-2.7GHz 

10V/m 

Criterion 

 

Fast transients (Burst) 

EN 61000-4-4 

Input lines 
Output lines 

4kV 
2kV 

Criterion A 
Criterion A 

 

Surge voltage on input 

EN 61000-4-5 

Æ

 N 

N / L 

Æ

 PE 

2kV  
4kV 

Criterion A 
Criterion A 

 

Surge voltage on output 

EN 61000-4-5 

Æ

 - 

+ / - 

Æ

 PE 

500V 
500V 

Criterion A 
Criterion A 

  Conducted disturbance 

EN 61000-4-6 

0,15-80MHz 

10V 

Criterion A 

 

Mains voltage dips 

EN 61000-4-11 

0% of 100Vac

 

40% of 100Vac 
70% of 100Vac  
0% of 200Vac

 

40% of 200Vac 
70% of 200Vac 

0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 

Criterion A 
Criterion C 
Criterion A 
Criterion A 
Criterion A 
Criterion A 

  Voltage interruptions 

EN 61000-4-11 

 

0Vac, 5000ms 

Criterion C 

  Input voltage swells 

PULS internal standard 

 

300Vac, 500ms 

Criterion A 

 

Powerful transients 

VDE 0160 

Over entire load 
range 

750V, 1.3ms 

Criterion A 

Criterions:

 

A:

  Power supply shows normal operation behavior within the defined limits.  

C:

  Temporary loss of function is possible. Power supply might shut-down and restarts by itself. No damages or hazards to the power 

supply will occur. 

 

 

EMC Emission

 

EN 61000-6-3, EN 61000-6-4 

Generic standards 

  Conducted emission  

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 

Class B, input lines 

   

EN 55022 

Class B, output lines  

  Radiated emission 

EN 55011, EN 55022 

Class B 

 

Harmonic input current 

EN 61000-3-2  

Not applicable  
(below 75W input power) 

  Voltage fluctuations, flicker EN 

61000-3-3 

 

Fulfilled 

 

This device complies with FCC Part 15 rules.  
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 

 

 

 

Switching frequency

 

constant, typ. 65kHz 

 

 

 

Summary of Contents for MiniLine ML15.121

Page 1: ...230Vac Temperature range 10 C to 70 C Operational Derating 0 4W C 60 to 70 C Hold up time typ 46 191ms At 120 230Vac Dimensions 22 5x75x91mm WxHxD A compact size light weight simple mounting onto the...

Page 2: ...pply shall only be installed and put into operation by qualified personnel This power supply is designed for installation in an enclosure and is intended for the general use such as in industrial cont...

Page 3: ...t 12V 1 3A Start up delay typ 780ms 780ms 780ms See Fig 5 2 Rise time typ 12ms 12ms 12ms At 12V 1 3A see Fig 5 2 Turn on overshoot max 100mV 100mV 100mV See Fig 5 2 The power factor is the ratio of th...

Page 4: ...the first peak Input Voltage Input Current Input Current Input 230Vac Output 12V 1 3A Ambient 25 C Upper curve Input current 5A DIV Lower curve Input voltage 500V DIV Time scale 10ms DIV Input 230Vac...

Page 5: ...ange min 85 375Vdc Continuous operation DC input current typ 0 16A 0 057A 110Vdc 300Vdc at a load of 12V and 1 3A Turn on voltage typ 80Vdc Steady state value Shut down voltage typ 60Vdc Steady state...

Page 6: ...mode See Fig 9 2 max Hiccup mode See Fig 9 2 Fig 9 1 Output voltage vs output current typ Fig 9 2 Hiccup mode Output current at shorted output 230V typ Output Voltage 0 0 2 4 6 16V 8 10 12 2 0A 1 0 0...

Page 7: ...f load typ 3 4W 3 2W 3 1W 1 3A 12V full load Fig 10 1 Efficiency vs output current at 12V Fig 10 2 Losses vs output current at 12V Efficiency 0 2 77 78 79 80 81 82 83 76 84 1 4A 0 6 0 8 1 2 Output Cur...

Page 8: ...ars 15 years 15 years 25 C 12V 1 3A MTBF SN 29500 IEC 61709 3 435 000h 3 723 000h 3 811 000h 40 C 12V 1 3A 5 633 000h 6 106 000h 6 205 000h 25 C 12V 1 3A MTBF MIL HDBK 217F 1 482 000h 1 534 000h 1 451...

Page 9: ...er Turn to set the output voltage Factory setting is 12 0V 14 TERMINALS AND WIRING All terminals are easy to access when mounted on the panel Input and output terminals are separated from each other i...

Page 10: ...of 100Vac 40 of 100Vac 70 of 100Vac 0 of 200Vac 40 of 200Vac 70 of 200Vac 0Vac 20ms 40Vac 200ms 70Vac 500ms 0Vac 20ms 80Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion...

Page 11: ...6000m Degree of pollution 2 EN 50178 IEC 62103 non conductive Fig 16 1 Output power vs ambient temperature Fig 16 2 Output power vs altitude 0 10 0 20 40 70 C 2 5 5 0 7 5 10 0 12 5 15W 60 Ambient Temp...

Page 12: ...terminal connected to Protective earth 2 Functional earth terminal not connected 19 DIELECTRIC STRENGTH Fig 19 1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac...

Page 13: ...Division 2 wiring methods of the National Electrical Code NFPA 70 and in accordance with other local or national codes CSA R 182790 C US CSA approval for Canada CAN CSA C22 2 No 107 1 CAN CSA 60950 1...

Page 14: ...see chapter 25 12 An appropriate electrical and fire end product enclosure should be considered in the end use application Cooling Convection cooled no forced cooling required Do not cover ventilation...

Page 15: ...dips Fig 25 1 Peak load 2 6A for 50ms typ Fig 25 2 Peak load 6 5A for 5ms typ 10ms DIV Output Voltage Output Current 12V 0A 2 6A 7 8V 1ms DIV Output Voltage Output Current 12V 0A 6 5A 2V Peak load 2...

Page 16: ...quired when the sum of the output voltage is above 60Vdc Note Avoid return voltage e g from a decelerating motor or battery which is applied to the output terminals 25 5 PARALLEL USE TO INCREASE OUTPU...

Page 17: ...ing module MLY02 100 Other recommendations for building redundant power systems a Use separate input fuses for each power supply b Set the output voltage of the power supplies approx 1V higher to comp...

Page 18: ...side caused by the input are much smaller compared to not connecting the FE terminal to ground Therefore we recommend to connect the FE terminal too ground Fig 25 5 Functional earth terminal connected...

Page 19: ...mperature for the power supply Results from such an installation Power supply is placed in the middle of the box no other heat producing equipment inside the box Enclosure Rittal Type IP66 Box PK 9510...

Page 20: ...ve A1 Recommended output power Curve A2 Max allowed output power results approx in half the lifetime expectancy of A1 Fig 25 8 Mounting Orientation A Standard Orientation Power Supply OUTPUT INPUT Out...

Reviews: