background image

 

 

 

ML15.121 

 

MiniLine

 

 

12V, 1.3A, S

INGLE 

P

HASE 

I

NPUT

 

 

 

Dec. 2007 / Rev. 1.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

1/20 

 

P

OWER 

S

UPPLY

 

 

100-240V Wide Range Input 

 

NEC Class 2 Compliant 

 

Adjustable Output Voltage 

 

Efficiency up to 83.6% 

 

Compact Design, Width only 22.5mm 

 

Full Output Power Between -10°C and +60°C 

 

Large International Approval Package 

 

3 Year Warranty 

 

 

1. G

ENERAL 

D

ESCRIPTION

 

 

2. S

HORT

-

FORM 

D

ATA

 

Output voltage 

DC 12V 

 

Adjustment range 

12-15V 

 

Output current 

1.3–1.0A 

12-15V 

 

 

 

Output power 

15W 

 

 

 

 

Output ripple 

< 75mVpp 

20Hz to 20MHz 

Input voltage 

AC 100-240V 

Wide Range Input 

Mains frequency 

50-60Hz  

±6% 

AC Input current 

typ. 0.28 / 0.17A  At 120 / 230Vac 

Power factor 

typ. 0.51 / 0.44 

At 120 / 230Vac 

AC Inrush current 

16 / 31A 

Typ. peak value  
at 120 / 230Vac 
40°C and cold start 

DC Input 

85-375Vdc 

 

Efficiency 

typ. 83.0 / 83.6%  At 120 / 230Vac 

Losses 

typ. 3.2 / 3.1W 

At 120 / 230Vac 

Temperature range  -10°C to +70°C 

Operational 

Derating 

0.4W/°C 

+60 to +70°C 

Hold-up time 

typ. 46 / 191ms 

At 120 / 230Vac 

Dimensions 22.5x75x91mm 

WxHxD 

A compact size, light weight, simple mounting onto 
the DIN-rail and the utilization of only quality 
components are what makes the MiniLine power 
supplies so easy to use and install within seconds. 

A rugged electrical and mechanical design as well as 
a high immunity against electrical disturbances on 
the mains provides reliable output power. This offers 
superior protection for equipment which is 
connected to the public mains network or is exposed 
to a critical industrial environment. 

The MiniLine series offers output voltages from 5 to 
56Vdc and a power rating from 15W to 100W. 

The supplementary MiniLine decoupling diode 
module MLY02.100 allows building of redundant 
systems or to protect against back-feed voltages. 

ML15.241

ML15.121

ML15.051

ML30.100

5V

Output

ML15

Related products

More

Power

12V

Output

24V Output

 

 

 

 

 

 

3. O

RDER 

N

UMBERS

 

 

4. M

ARKINGS

 

 Power 

supply 

ML15.121 

Standard unit 

  

 

 

IND. CONT. EQ.

18WM

LISTED

 

UL 508 

 

UL 60950-1 

 

Class I Div 2 

 

Accessory MLY02.100 

Decoupling 

Redundancy module 

  

 

 

 

 

R

182790

C

US

 

GL

 

Marine 

 

EMC, LVD 

Summary of Contents for MiniLine ML15.121

Page 1: ...230Vac Temperature range 10 C to 70 C Operational Derating 0 4W C 60 to 70 C Hold up time typ 46 191ms At 120 230Vac Dimensions 22 5x75x91mm WxHxD A compact size light weight simple mounting onto the...

Page 2: ...pply shall only be installed and put into operation by qualified personnel This power supply is designed for installation in an enclosure and is intended for the general use such as in industrial cont...

Page 3: ...t 12V 1 3A Start up delay typ 780ms 780ms 780ms See Fig 5 2 Rise time typ 12ms 12ms 12ms At 12V 1 3A see Fig 5 2 Turn on overshoot max 100mV 100mV 100mV See Fig 5 2 The power factor is the ratio of th...

Page 4: ...the first peak Input Voltage Input Current Input Current Input 230Vac Output 12V 1 3A Ambient 25 C Upper curve Input current 5A DIV Lower curve Input voltage 500V DIV Time scale 10ms DIV Input 230Vac...

Page 5: ...ange min 85 375Vdc Continuous operation DC input current typ 0 16A 0 057A 110Vdc 300Vdc at a load of 12V and 1 3A Turn on voltage typ 80Vdc Steady state value Shut down voltage typ 60Vdc Steady state...

Page 6: ...mode See Fig 9 2 max Hiccup mode See Fig 9 2 Fig 9 1 Output voltage vs output current typ Fig 9 2 Hiccup mode Output current at shorted output 230V typ Output Voltage 0 0 2 4 6 16V 8 10 12 2 0A 1 0 0...

Page 7: ...f load typ 3 4W 3 2W 3 1W 1 3A 12V full load Fig 10 1 Efficiency vs output current at 12V Fig 10 2 Losses vs output current at 12V Efficiency 0 2 77 78 79 80 81 82 83 76 84 1 4A 0 6 0 8 1 2 Output Cur...

Page 8: ...ars 15 years 15 years 25 C 12V 1 3A MTBF SN 29500 IEC 61709 3 435 000h 3 723 000h 3 811 000h 40 C 12V 1 3A 5 633 000h 6 106 000h 6 205 000h 25 C 12V 1 3A MTBF MIL HDBK 217F 1 482 000h 1 534 000h 1 451...

Page 9: ...er Turn to set the output voltage Factory setting is 12 0V 14 TERMINALS AND WIRING All terminals are easy to access when mounted on the panel Input and output terminals are separated from each other i...

Page 10: ...of 100Vac 40 of 100Vac 70 of 100Vac 0 of 200Vac 40 of 200Vac 70 of 200Vac 0Vac 20ms 40Vac 200ms 70Vac 500ms 0Vac 20ms 80Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion...

Page 11: ...6000m Degree of pollution 2 EN 50178 IEC 62103 non conductive Fig 16 1 Output power vs ambient temperature Fig 16 2 Output power vs altitude 0 10 0 20 40 70 C 2 5 5 0 7 5 10 0 12 5 15W 60 Ambient Temp...

Page 12: ...terminal connected to Protective earth 2 Functional earth terminal not connected 19 DIELECTRIC STRENGTH Fig 19 1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac...

Page 13: ...Division 2 wiring methods of the National Electrical Code NFPA 70 and in accordance with other local or national codes CSA R 182790 C US CSA approval for Canada CAN CSA C22 2 No 107 1 CAN CSA 60950 1...

Page 14: ...see chapter 25 12 An appropriate electrical and fire end product enclosure should be considered in the end use application Cooling Convection cooled no forced cooling required Do not cover ventilation...

Page 15: ...dips Fig 25 1 Peak load 2 6A for 50ms typ Fig 25 2 Peak load 6 5A for 5ms typ 10ms DIV Output Voltage Output Current 12V 0A 2 6A 7 8V 1ms DIV Output Voltage Output Current 12V 0A 6 5A 2V Peak load 2...

Page 16: ...quired when the sum of the output voltage is above 60Vdc Note Avoid return voltage e g from a decelerating motor or battery which is applied to the output terminals 25 5 PARALLEL USE TO INCREASE OUTPU...

Page 17: ...ing module MLY02 100 Other recommendations for building redundant power systems a Use separate input fuses for each power supply b Set the output voltage of the power supplies approx 1V higher to comp...

Page 18: ...side caused by the input are much smaller compared to not connecting the FE terminal to ground Therefore we recommend to connect the FE terminal too ground Fig 25 5 Functional earth terminal connected...

Page 19: ...mperature for the power supply Results from such an installation Power supply is placed in the middle of the box no other heat producing equipment inside the box Enclosure Rittal Type IP66 Box PK 9510...

Page 20: ...ve A1 Recommended output power Curve A2 Max allowed output power results approx in half the lifetime expectancy of A1 Fig 25 8 Mounting Orientation A Standard Orientation Power Supply OUTPUT INPUT Out...

Reviews: