CS10.241, CS10.241-S1
CS-Series
24V,
10A,
240W
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/27
6.
O
UTPUT
Output voltage
nom.
24V
Adjustment range
24-28V
guaranteed
max.
30V
***)
at clockwise end position of potentiometer
Factory settings
typ.
24.1V
±0.2%, at full load, cold unit
Line regulation
max.
70mV
90-132 / 180-300Vac
Load regulation
max.
100mV
static value, 0A
→
10A; see Fig. 6-1
Ripple and noise voltage
max.
50mVpp
20Hz to 20MHz, 50Ohm
Output current
nom.
10A
at 24V and up to +60°C ambient temperature, see Fig. 6-1
nom.
7.5A
at 24V and +70°C ambient temperature
nom.
8.6A
at 28V and up to +60°C ambient temperature, see Fig. 6-1
nom.
6.5A
at 28V and +70°C ambient temperature
Derate linearly b60°C and +70°C, see chapter 14
PowerBoost
*)
nom.
12A
at 24V and up to +45°C ambient temperature, see Fig. 14.1
nom.
10.3A
at 28V and up to +45°C ambient temperature, see Fig. 14.1
PowerBoost decreases linearly to nominal power b45°C and +60°C, see chapter 14
Overload behavior
continuous current
Short-circuit current
min.
14A
**)
load impedance <100mOhm, see Fig. 6-1
max.
18A
**)
load impedance <100mOhm, see Fig. 6-1
Output capacitance
typ.
7 000µF
included inside the power supply
*)
PowerBoost
This power/ current is continuously allowed up to an ambient temperature of +45°C.
Above +45°C, do not use this power/ current longer than a duty cycle of 10% and / or not longer than 1 minute every 10 minutes.
**)
Discharge current of output capacitors is not included.
***)
This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value
which can be achieved. The typical value is about 28.5V.
Fig. 6-1
Output voltage vs. output current, typ.
Output Voltage
0
0
4
8
12
16
4
8
12
28V
16
20
24
20A
10
6
2
14
18
Adjustment
Range
Output Current
+60°C
+25°C
-25°C