CS10.241, CS10.241-S1
CS-Series
24V,
10A,
240W
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/27
14.
E
NVIRONMENT
Operational temperature
*)
-25°C to +70°C
reduce output power according Fig. 14-1
Storage temperature
-40°C to +85°C
for storage and transportation
Output derating
6W/K
B60°C and +70°C
Humidity
**)
5 to 95% r.h.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
***)
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m
without any restrictions
2000 to 6000m
reduce output power or ambient temperature,
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude derating
15W/1000m or 5K/1000m
for altitudes >2000m, see Fig. 14-2
Over-voltage category
III
IEC 62103, EN 50178, altitudes up to 2000m
II
altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
*)
Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
Fig. 14-1
Output current vs. ambient temp.
(Inom 10A; Iout with PowerBoost = 12A)
Fig. 14-2
Output current vs. altitude
0
-25
0
20
40
70°C
2
4
6
8
10
12A
60
Ambient Temperature
Allowable Output Current at 24V
A
A...90-132/ 180-264Vac, continuous
B... short term
B
0
0
2000
4000
6000m
2
4
6
8
10
12A
Altitude
Allowable Output Current at 24V
B
C
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
D... Short t erm
A
D