CS10.241, CS10.241-S1
CS-Series
24V,
10A,
240W
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev. 2.1 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/27
P
OWER
S
UPPLY
▪
AC 100-120 / 200-240V Auto-select Input
▪
Width only 60mm
▪
Optional with Spring-clamp Terminals (CS10.241-S1)
▪
Efficiency up to 91.6%
▪
Easy Fuse Breaking due to High Overload Peak Current
▪
20% Output Power Reserves (PowerBoost)
▪
Full Power Between -25°C and +60°C
▪
Minimal Inrush Current Surge
▪
3 Year Warranty
P
RODUCT
D
ESCRIPTION
The DIMENSION CS-Series units are cost optimized power
supplies without compromising
quality,
reliability and
performance. The CS-Series is part of the DIMENSION power
supply family, existing alongside the high featured Q-Series.
The CS10.241 includes all the essential basic functions. The
devices also offer PowerBoost: Power reserves of 20%, which
may even be used continuously at temperatures up to +45°C.
The most important features are the small size, high efficiency
and the wide temperature range.
The Auto-select input makes worldwide installation and usage
very simple. Defects or system failures caused by wrongly set
switches cannot occur.
High immunity to transients and power surges as well as low
electromagnetic emission and a large international approval
package for a variety of applications makes this unit suitable for
nearly every situation.
S
HORT
-
FORM
D
ATA
Output voltage
DC 24V
Adjustment range
24 - 28V
Output current
10A
up to +60°C ambient
8.6A
at +70°C ambient
Derate linearly b60°C and +70°C
PowerBoost
12A
up to +45°C ambient
Linear decrease to nominal power
b45°C and +60°C
Output ripple
< 50mVpp
20Hz to 20MHz
AC Input voltage
AC 100-120V /
200-240V
±10%
Auto-select input
Mains frequency
50-60Hz
±6%
AC Input current
3.73 / 2.23A
at 120 / 230Vac
DC Input voltage
-
not allowed
Power factor
0.59 / 0.51
at 120 / 230Vac
AC Inrush current
3 / 3A peak
at 120 / 230Vac
Efficiency
91.0 / 91.6%
at 120 / 230Vac
Losses
23.7 / 22.0W
at 120 / 230Vac
Temperature range
-25°C to +70°C
operational
Hold-up time
46 / 47ms
at 120 / 230Vac
Dimensions
60x124x117mm
WxHxD
Weight
700g
O
RDER
N
UMBERS
Power Supply
CS10.241
24-28V Standard unit
CS10.241-S1
Version with quick-
connect spring-clamp
terminals
Accessory
ZM1.WALL
Wall mount bracket
ZM13.SIDE
Side mount bracket
YRM2.DIODE
Redundancy module
YR40.241
Redundancy module
M
AIN
A
PPROVALS
For details and the complete approval list, see chapter 18.
UL 508
UL 60950-1
Class I Div 2
Marine
Marine