CS20.241, CS20.241-A1
C-Series
24V,
20A,
S
INGLE
P
HASE
I
NPUT
Preliminary
7.
H
OLD
-
UP
T
IME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
65ms
65ms
65ms
at 24V, 10A, see Fig. 7-1
min.
54ms
54ms
54ms
at 24V, 10A, see Fig. 7-1
typ.
29ms
29ms
29ms
at 24V, 20A, see Fig. 7-1
min.
24ms
24ms
24ms
at 24V, 20A, see Fig. 7-1
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
10
20
30
40
80ms
90
120
155
190
230Vac
Input Voltage
50
60
Hold-up Time
24V, 20A, typ.
24V, 10A, min.
24V, 10A, typ.
70
24V, 20A, min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
8.
DC-OK
R
ELAY
C
ONTACT
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed
voltage from a unit connected in parallel to the power supply output.
Contact closes
As soon as the output voltage reaches 90% of the adjusted output voltage level.
Contact opens
As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Contact ratings
max.
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A
resistive load
min.
1mA at 5Vdc
min. permissible load
Isolation voltage
See dielectric strength table in section 18.
Fig. 8-1
DC-ok relay contact behavior
100ms
0.9* V
ADJ
<
1ms
10%
open
V
OUT
= V
ADJ
open
closed
closed
>
1ms
Jan. 2012 / Rev. 0.5 DS-CS20.241-EN
Preliminary
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/25