ML60.122
MiniLine-2
12V,
4.5A,
S
INGLE
P
HASE
I
NPUT
14.
E
NVIRONMENT
Operational temperature
*)
-40°C to +70°C (-40°F to 158°F)
reduce output power according Fig. 14-1
Storage temperature
-40°C to +85°C (-40°F to 185°F)
for storage and transportation
Output de-rating
1.4W/°C
60-70°C (140°F to 158°F)
Humidity
**)
5 to 95% r.H.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock
15g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m (0 to 6 560ft)
without any restrictions
2000 to 6000m (6 560 to 20 000ft)
reduce output power or ambient temperature
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating
4W/1000m or 5°C/1000m
> 2000m (6500ft), see Fig. 14-2
Over-voltage category
III
IEC 62103, EN 50178, altitudes up to 2000m
II
altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
Do not connect or disconnect the wires from the terminals below -25°C.
**) Do not energize while condensation is present
Fig. 14-1
Output power vs. ambient temp.
Fig. 14-2
Output power vs. altitude
0
12/23
-40
0
40
70°C
10
20
30
40
50
60W
60
A... for AC 230V mains
B... for AC 120V mains
C... for AC 100V mains
-25
-33
Ambient Temperature
Allowable
Output Power
A
C
B
0
0
2000
4000
6000m
10
20
30
40
50
60W
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable
Output Power
Nov. 2015 / Rev. 1.4 DS--ML60.122-EN
All parameters are specified at 12V, 4.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany