background image

 

 

PISA11.CLASS2

 

 

 

PISA11-Series 

P

ROTECTION 

M

ODULE 

24V,

 

4

 

O

UTPUTS

 

 

 

4.

 

I

NPUT

 

 

Input voltage 

nom. 

DC 24V 

±25% 

Input voltage range 

18Vdc – 30Vdc 

 

 

max. 

30Vdc 

Absolute maximum continuous input voltage with no 
damage to the PISA module 

Turn-on voltage 

typ. 

21.4Vdc 

Required input voltage for turning-on the outputs 

Turn-on delay of outputs 

typ. 

270ms 

Period between applying the input voltage and turning 
on the outputs. All outputs will be turned-on at the 
same time. 

Input voltage protection level 

*)

 min. 

max. 

21.0Vdc 
21.8Vdc 

Below this voltage level, outputs will shutdown. 

Stand-by input current 

typ. 

43mA 

Stand-by current with no load current on the outputs 

*) 

Voltage dips below this value can occur for maximal 200μs. 

 

 

5.

 

O

UTPUTS

 

 

 

 

24V Input 

28V Input 

 

Output current 

output 1 

nom. 

3.7A 

3.2A 

see Fig. 5-1

 

 output 

nom. 

3.7A 

3.2A 

see 

Fig. 5-1

 

 output 

nom. 

3.7A 

3.2A 

see 

Fig. 5-1

 

 output 

nom. 

3.7A 

3.2A 

see 

Fig. 5-1

 

All 4 outputs together 

nom. 

14.8A 

12.8A 

 

Output current limitation

 *)

 min. 

16.6A 

16.6A 

 

 typ. 

19.9A 

19.9A 

 

 max. 

23.6A 

23.6A 

 

Voltage drop

 **)

 typ. 

92mV 

81mV 

 

Output leakage current 

***)

 typ. 

0.4mA 

0.4mA  0.4mA 

*) 

The current limitation value for the sum of all four output currents. This current can be drawn from each individual output before the 
protection module shutdown all four outputs at the same time. Shutdown times can be found in chapter 6. 

**)  Voltage loss between input and output, when all output channels are loaded with 50% of its nominal current. 
***) Output current when outputs have shut down 

 

 

Fig. 5-1

   Output current vs. input voltage 

 

 

 

Input
Voltage

22V

0

1A

3A

4A

24V

25V

26V

30V

27V

28V

29V

2A

23V

Output Current, typ

 

 

May 2014 / Rev. 1.7  DS-PISA11.CLASS2 - data sheet - 
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278-0    Germany 

5/19

Summary of Contents for PISA11 Series

Page 1: ...en they are connected directly to the same power supply as the PISA module Less critical loads that are not affected to short voltage interruptions or that could even be the cause of a fault on the 24V power supply are connected to one of the four NEC CLASS 2 output channels of the PISA module SHORT FORM DATA Input voltage DC 24V Input voltage range 18 30V Input current typ 43mA At no load Number ...

Page 2: ...ing Bracket 19 The information presented in this document is believed to be accurate and reliable and may change without notice The housing is patent by PULS US patent No US D442 923S No part of this document may be reproduced or utilized in any form without permission in writing from the publisher PULS GmbH This also applies to all kinds of electronic publishing TERMINOLOGY AND ABREVIATIONS DC 24...

Page 3: ...t voltage does not drop below 21V In case the input voltage would fall below this value e g due to overloads too small of a power supply or high inrush currents such as from starting a motor all four output channels will be actively current limited and will shutdown after a certain period of time A typical wiring configuration is shown below All sensitive loads are connected directly to the power ...

Page 4: ...Load 1 WARNING Risk of electrical shock fire personal injury or death Turn power off before working on the device Protect against inadvertent re powering Make sure that the wiring is correct by following all local and national codes Do not modify or repair the unit Do not open the unit Use caution to prevent any foreign objects from entering the housing Do not use in wet locations or in areas wher...

Page 5: ...A see Fig 5 1 output 3 nom 3 7A 3 2A see Fig 5 1 output 4 nom 3 7A 3 2A see Fig 5 1 All 4 outputs together nom 14 8A 12 8A Output current limitation min 16 6A 16 6A typ 19 9A 19 9A max 23 6A 23 6A Voltage drop typ 92mV 81mV Output leakage current typ 0 4mA 0 4mA 0 4mA The current limitation value for the sum of all four output currents This current can be drawn from each individual output before t...

Page 6: ...ed output current At 2 times the rated current typ 1s at 7 4A At short circuit typ 10ms The timer for shutdown starts immediately once the rated current levels are exceeded All output channels will shutdown if one channel is overloaded See Fig 6 1 for more values A shutdown of the outputs can also happen earlier e g when the PISA module has to protect the supply voltage in case the power supply ca...

Page 7: ...s All four outputs will shutdown simultaneously Shutdown times for a short circuit condition across the outputs can be found in Fig 6 2 Fig 6 2 Active current limitation Period of time in current limiting mode until the outputs will shutdown Adjustable Power Supply Load I 0 8 IOUT Short IOUT PISA Module Test Setup IOUT 10ms 100ms 1s 10s 2A 4A 6A 8A 10A 12A 14A 16A 18A 20A 45 C Output Current Sum c...

Page 8: ...tive load See also the parameter list below the table Permissible Capacitors PISA11 CLASS2 Per channel 58mF 14mF All four outputs together typ 58mF min 14mF Parameters Typical values are with an additional 1 9A resistive load per output Minimum values are with an additional 3 7A constant current load per output Case B Only one output is loaded The minimum values for the permissible capacitors are ...

Page 9: ... max 10Vdc reset Galvanic isolation nom 500Vac Test voltage signal path to power path 10 SYNCHRONIZATION OF MULTIPLE PISA MODULES If multiple PISA modules are used on the same power supply it is recommended to connect the sync bus of all modules together If one unit shuts down due to the protection function of the input voltage protection circuit safeguard all other modules will shutdown too This ...

Page 10: ...This feature is also called return voltage immunity or resistance against Back E M F Electro Magnetic Force The protection module is resistant and does not show malfunctioning when a load feeds back voltage up to 30Vdc to the protection module It does not matter whether the protection module is on or off The protection module has no capability to absorb energy Internal diodes integrated body diode...

Page 11: ...culated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliabi...

Page 12: ...protection function of the input voltage protection circuit all other modules will shutdown too This avoids a false interpretation of which output channel caused the problem If the cause for the shutdown was an over current of one individual channel only this module will shutdown and the other modules will stay on In this case the sync line has no impact on the other modules E Output OK Relay Cont...

Page 13: ...orque 0 8Nm 7lbs in 0 35Nm 3lbs in Instructions a Use NEC Class 2 rated wires for the output b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and minimum 75 C for ambient up to 60 C and minimum 90 C for ambient up to 70 C c Follow national installation codes and installation regulations d Ensure that all strands of a stranded wire ...

Page 14: ...kV 500V 1kV Criterion A Criterion A Surge voltage on output lines EN 61000 4 5 Æ Æ DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on signal lines EN 61000 4 5 DC OK Æ DIN Rail 1kV 1kV Criterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V 10V Criterion A Criterion A The PISA protection module shows normal operation behavior within the defined limits on coupling plane EMC E...

Page 15: ...ctive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint shops Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit Do not energize while condensation is present Tested in combination with DIN Rails according to EN 60715 with a height of 15mm and a thickness ...

Page 16: ...FF signal input and input output voltage are 1 3mm The following dielectric strength tests were conducted Fig 20 1 Dielectric strength A B C Type test 60s 500Vac 500Vac 50Vac Factory test 5s 500Vac 500Vac Field test 5s 500Vac 500Vac 50Vac Cut off current setting 1mA 1mA 1mA A C B Output ok Contact Reset ON OFF Signal Input Input Output 1 4 Sync 15 16 13 14 12 11 Type and factory tests are conducte...

Page 17: ...50 1 Also meet the requirements of NEC CLASS 2 according to UL1310 UL 2367 Special purpose Solid State Overcurrent Protector Component Recognition UL Category QVRQ2 E File E342020 ANSI ISA 12 12 01 2007 Class I Div 2 LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems NRTL C Canada and U S EN 60079 15 ATEX II 3G EX nA nC IIC T4 Gc Approval for use in hazardous locations Zo...

Page 18: ... four red LEDs shows the firmware revision level Revision level LED 1 LED 2 LED 3 LED 4 A OFF OFF OFF ON B OFF OFF ON OFF C OFF OFF ON ON D OFF ON OFF OFF E OFF ON OFF ON F OFF ON ON OFF G OFF ON ON ON H ON OFF OFF OFF I ON OFF OFF ON J ON OFF ON OFF K ON OFF ON ON L ON ON OFF OFF M ON ON OFF ON N ON ON ON OFF O ON ON ON ON May 2014 Rev 1 7 DS PISA11 CLASS2 data sheet All parameters are specified ...

Page 19: ...IONS AND WEIGHT Weight 120g 0 26lb DIN Rail Use 35mm DIN rail according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN rail height must be added to the unit depth to calculate the total required installation depth Installation clearances See chapter 3 Fig 23 1 Front view Fig 23 2 Side view 24 ACCESSORY 24 1 ZM3 WALL WALL MOUNTING BRACKET bulk package with 25 pcs DIN Rail bracket for ...

Reviews: