background image

 

12286 Rev 2 

                Page 2 of 3 

3.1  Command Menu 

 

Explanation of Commonly Used Menu Entries 

Reference # & Menu Item  Function 

9)  Aux In 

This indicates the measured voltage from the analog input set point 
control.  This will reflect the voltage received at the TIM-100/120 from 
the equipment (5000 = 5.000 V). 

10) Pres Sp1 

For pressure exhaust controllers, this entry allows the pressure set 
point to be reviewed or edited.  For the SENTRY 1000, 2000 = 2.000” 
H

2

O.  For the SENTRY 1510, 2540 = 25.40 mm H

2

O. 

14) Flow Sp1 

For flow exhaust controllers, this entry allows the flow set point to be 
reviewed or edited. 

34) Pres FS 

For pressure exhaust controllers, this indicates the full pressure scale 
for the exhaust control device. The full scale must match the 
pressure transducer inside the control device. 

35) Flow FS 

For flow exhaust controllers, this indicates the full flow scale achiev-
able by the control device. 

37) Aux FS 

This indicates the full scale of the analog signal input.  When using a 
0-5 V control signal (analog interface), this item must be set to 5000, 
representing 5.000 V full scale. 

38) SaveData 

This is used to save the TIM-100/120 configuration to nonvolatile 
memory.  Refer to section 2, page for instructions on saving 
parameter changes. 

39) BaudRate 

This is used to set the RS422/RS485 serial port speed rate.  The 
process equipment controller or host computer  must use the same 
baud rate.  The TIM-100/120 can handle up to 9600 baud. 

40) Parity 

This item allows the selection of the following serial data parity:  Odd, 
Even, One, and Zero.  After changing parity, Save Data must be 
executed first and then power to the TIM-100/120 must be cycled 
once 

(On to Off to On).

 

51) GainFine 

This indicates the gain (proportional) coefficient that is used in the 
PID loop This indicates the same value as the “Gain” menu item but 
allows the operator a finer increment of adjustment. 

55) Deadband 

This indicates the band on either side of the set point, within which 
the process variable can move and not cause control loop action. 

68) StptMode 

This is used to define where the controller receives its set point.  The 
selections are single, analog, dual and quad.  Single indicates a 
single digital set point from an RS422/RS485 serial connection or 
manually set by the user.  This set point is the value under Pres Sp1.  
Analog indicates a remote set point, through a 0-5 V analog interface.  
Dual and Quad are not used. 

69) OperMode 

This indicates the process parameter to be controlled.  Pressure is 
indicated by Pres, flow is indicated by Flow. 

 

Summary of Contents for SENTRY TIM-100

Page 1: ...100 120 is a microprocessor based interface used in conjunction with many of Progressive Technologies Inc process exhaust controllers The SENTRY TIM 100 120 allows the user to communicate electronically with the process exhaust controller such as the SENTRY 1000 for changing the set point and reading actual process exhaust values It can be configured at the PTI factory to be used with controllers ...

Page 2: ...cess equipment Mounting Brackets are used to mount the TIM 100 120 to the process equipment ƒ ƒ Display provides a real time read back of pressure control It also allows the user to view and change the menu parameters Keypad contains the four keys used to navigate and change the menu tree and parameters Contrast Knob allows the user to adjust the display contrast Power Interface Port accepts the p...

Page 3: ...ont cover must be removed for access to the receptacle Keypad TIM 100 200 Asterisk Key Asterisk key enables a menu item to be modified When the star key is depressed on the keypad An will appear in the selection indicator box see page 8 ƒ ƒ Up Arrow á á and Down Arrow â â Keys Arrow keys allow the user to scroll through the menu items Once a menu item is chosen using the asterisk key the arrow key...

Page 4: ...for details Menu Item Value The menu item value display indicates the current set value for the menu item displayed Process Exhaust Actual Read Back The label Pres or Flow on the display indicates whether the read back is in units of pressure or flow The number indicates the currently achieved actual process exhaust read back Depending on the SENTRY model this value will indicate pressure in H2O m...

Page 5: ...h the TIM 100 and TIM 120 are equipped with 4 holes for panel mounting as shown Power Requirements The SENTRY TIM 100 120 operates using both positive and negative DC voltages DC Voltages may be supplied directly from the equipment via an interface cable or through a stand alone universal power supply available from PTI Note In case of AC over current situations the SENTRY system relies upon the p...

Page 6: ...ing Connect Program Module If Required The TIM 120 is shipped pre configured for use with the SENTRY system The Program Module provides keypad access and LCD readout similar to a TIM 100 The Program Module is only required for the TIM 120 if selecting alternate communication protocols or menu parameters Remove the four screws and the faceplate from the front of the TIM 120 Connect the Program Modu...

Page 7: ...ing stand alone operation or serial interface communication or choose ANALOG if using analog interface communication Press the enter ENT key to confirm selection Save Operating Parameter Data Any change made to the menu items is stored in memory until the power to the TIM 100 120 is turned off To permanently store selections into memory the following steps must be taken Using the up á or down â ar...

Page 8: ...irs The RS 422 communication link uses a four wire Tx Tx Rx Rx connection Two wires are used to send from the host two wires are used to receive by the host The serial communication interface cable is a six wire cable The TIM 100 120 end of the cable is crimped with a RJ 12 6 pin male connector The other end is maintained with labeled flying leads Pin Function Comment 1 Rx Receive from host Positi...

Page 9: ...NTRY TIM 100 120 Command Menu 1 Sentry Ver 20 Pos Sp3 39 BaudRate 58 StepRate 2 Pres Sp 21 Pos Sp4 40 Parity 59 PulWidth 3 Flow Sp 22 Usage 1 41 HWCtlLck 60 StepRang 4 Pos Sp 23 Usage 2 42 Ctl Itvl 61 Step Lim 5 Pres 24 Usage 3 43 CtrlLock 62 Step Req 6 Flow 25 Usage 4 44 FlowCoef 63 PlotItvl 7 Step Cnt 26 Select 45 FlwCfCrs 64 PlotMode 8 HouseVac 27 Alarms 46 FiltRate 65 Plot Sel 9 Aux In 28 Dev ...

Page 10: ... memory Refer to section 2 page for instructions on saving parameter changes 39 BaudRate This is used to set the RS422 RS485 serial port speed rate The process equipment controller or host computer must use the same baud rate The TIM 100 120 can handle up to 9600 baud 40 Parity This item allows the selection of the following serial data parity Odd Even One and Zero After changing parity Save Data ...

Page 11: ...back Flow and full scale flow Flow FS have an implied decimal point to the right of the first digit from the right No scaling factor is used The implied units are in cubic feet per minute Example The displayed value 12 equals 12 CFM Modes of Operation The TIM 100 120 is factory configured to operate in Pressure Mode SENTRY 1000 and SENTRY 1510 or Flow Mode SENTRY 9000 depending on the type of exha...

Page 12: ...t and parameters Description of the keys is located in Section 1of this manual Note Any change made to a menu item is only activated after the enter key is depressed Any change made to the menu item is only stored in memory until the next time the TIM 100 120 is powered off and on To permanently store values in memory follow the steps in Section of this manual Manual Mode Pressure Set Point Change...

Page 13: ...peration When the SENTRY system is configured for analog operation the process exhaust pressure or flow set points are entered through the process equipment The analog interface operates on a standard 0 to 5 volt full scale command signal Note The menu item STPTMODE must be set to ANALOG in order to use analog communication Refer to Section 2 page3 for details The menu item AUX IN will reflect the...

Page 14: ...Process exhaust flow read back The read back voltage returned by the SENTRY TIM 100 120 to the tool is proportional to the actual measured flow determined by the following equation Measured Process Exhaust Flow Flow FlowFS Aux FS Serial Interfaced Operation When the SENTRY system is configured for serial communication operation the process exhaust pressure or flow set points are entered through th...

Page 15: ...communications with the TIM 100 120 slave The communication protocol requires the host to send a command to the TIM 100 120 For each command sent the TIM 100 120 will respond with an acknowledgment message The communicated commands and acknowledgments are text strings made up of characters from the ASCII character set Note Up to 64 uniquely addressable TIM 100 120s can be connected on a given netw...

Page 16: ... Host to TIM 100 120 Command Message 00AA1 Function This message sends a power up clear command to the TIM 100 120 at base address 00 00AA1 Note If additional TIM 100 120s were connected on the same network each base address would be incremented by four Example 04AA1 08AA1 0CAA1 etc TIM 100 120 to Host Response A Function This response indicates an acknowledgement without error Set Point Using Com...

Page 17: ...fied 01S0100xxxyy If additional TIM 100 120s were connected on the same network each base address would be incremented by four Example 05S0100xxxyy Flow Set Point In order to write a flow set point to the TIM 100 120 the following command must be issued Host to TIM 100 120 Command Message 01S1000xxxyy Where xxx 000 to FFF representing a 0 to full scale range yy two hex character check sum Function...

Page 18: ...current pressure the following command must be issued to the TIM 100 120 Host to TIM 100 120 Command Message 01L00016E Function This message sends an interrogation to read the SENTRY TIM 100 120 pressure read back memory location The TIM 100 120 must be configured for pressure control i e SENTRY 1000 or SENTRY 1510 Note The SENTRY TIM 100 120 addressed is at base address 0 memory bank 1 01S00016E ...

Page 19: ...esenting the message checksum followed by a carriage return The checksum is computed by a adding the decimal values of all the ASCII characters in the message excluding the start of command character b dividing the sum by 256 and c converting the integer remainder to a two ASCII hex digits Example Command 08K012 Ignore the character ƒ Convert the remaining characters to decimal values Character He...

Page 20: ... parameters are selected for the controller installed TIM 100 120 parameter STPT MODE improperly set for installation Set TIM 100 120 parameter to Analog for analog communication or Single for stand alone or serial communication Analog Interface Analog interface improperly installed Properly install analog interface cable Serial Interface Serial cable improperly installed or address not set Proper...

Page 21: ...0 to 260 VAC 47 to 63 Hz Set Point Control Types 0 to 5 Volt Analog Interface RS422 485 Serial Interface up to 9600 baud Stand Alone Using Operator Keypad Cut Off Disconnect Devices Safety cut off device The SENTRY TIM 100 120 contains a cartridge fuse holder for a 5 X 20 mm fuse The fuse is a 0 8 amp fuse PTI part 12270 AC disconnect device The SENTRY TIM 100 120 relies upon the process tool or h...

Page 22: ...ing the host on a single network A repeater is required to add an additional 32 units for a maximum total of 64 SENTRY TIM 100 120s Communication Rate 9600 Baud Data 8 data bits Characters All messages between Host and SENTRY TIM 100 120s are made up of ASCII characters Parity No parity Start bit 1 start bit Stop bit 1 stop bit Protocol Two pass with a two character checksum for message transactio...

Page 23: ...t saved version It may be necessary to reinitialize the controller 01 Undefined command The command character that was received was not a legal command character 02 Checksum error The checksum received by the SENTRY did not match the sum of the characters in the command 03 Input Buffer Overrun The received command contained more than 71 characters for an analog com mand or 16 characters for a digi...

Page 24: ...Ctrl L 3C 6C l 0D Ctrl M 3D 6D m 0E Ctrl N 3E 6E n 0F Ctrl O 3F 6F o 10 Ctrl P 40 70 p 11 Ctrl Q 41 A 71 q 12 Ctrl R 42 B 72 r 13 Ctrl S 43 C 73 s 14 Ctrl T 44 D 74 t 15 Ctrl U 45 E 75 u 16 Ctrl V 46 F 76 v 17 Ctrl W 47 G 77 w 18 Ctrl X 48 H 78 x 19 Ctrl Y 49 I 79 y 1A Ctrl Z 4A J 7A z 1B Ctrl 4B K 7B 1C Ctrl 4C L 7C 1D Ctrl 4D M 7D IE Ctrl 4E N 7E 1F Ctrl _ 4F O 7F Del 20 Space 50 P Ctrl Null 21 ...

Page 25: ...6 6 6 Conversion Tables Hex to Binary Conversion Table Hex Binary Decimal 0 0000 0 1 0001 1 2 0010 2 3 0011 3 4 0100 4 5 0101 5 6 0110 6 7 0111 7 8 1000 8 9 1001 9 A 1010 10 B 1011 11 C 1100 12 D 1101 13 E 1110 14 F 1111 15 ...

Page 26: ... the SENTRY controller and SENTRY TIM 100 120 200 serial tags The part number and revision reference of the cables may be found on the label on each cable For your convenience please note the numbers below and retain this manual and information for future reference 1 SENTRY Controller Model Number Serial Number Rev Number 2 SENTRY TIM 100 120 Model Number Serial Number Rev Number 4 Tool Host to SE...

Page 27: ...tomer s improper use of the equipment lack of prescribed preventive maintenance failure of or caused by parts not supplied by PTI failure of or improper electrical power alteration or modification transportation vandalism fire chemicals or other casualty causes other than ordinary use improper servicing or reinstallation without prior written approval from PTI The sole responsibility and liability...

Reviews: