6
PSsystec SMARTbox IO Agent User Guide
Connect a Modbus Device to the SMARTbox
____________
The Smartbox supports Modbus RTU – all Connections parameters are configurable in the
Cloud.
Type
Modbus RTU (Master)
Cloud
Baudrate
4800, 9600, 19200, 38400, 115200 (Change during Runtime possible)
Modbus Tab
Parity
Even, ODD, NONE (Change during Runtime possible)
Modbus Tab
Stopbits
2,1 (Change during Runtime possible)
Modbus Tab
Functioncodes
Funct.1 (Read Single Coils)
Funct.2 (Read Input Status)
Funct.3 (Read Holding Registers)
Funct.4 (Read Input Registers)
Funct.5 (Write Coil)
Funct.6 (Write Holding Register)
Device database
(model)
Datapoints
1.. 10 Slaves with each 100 datapoints
fix
Polling Rate on
Bus
500ms
fix
We assume that you already defined your Modbus device(s) which you want to connect in
the device database. In this exemplary SetUp you need 4 Models in the device database,
which can and should be defined offline in the Cloud (see also chapter Help Device
database)
Device1: Chiller on Address1
Device2: Energy Meter on Address2
Device3: Frontcooler for Serverline1 on Address5
Device4: Frontcooler for Serverline2 on Address6