Step 4: 
 

After the device is shut down the MS1/GPS1 modules must be disconnected completely from the 
microPMU hardware as seen in the example image below. If the hardware is DIN rail mounted, slide the 
MS1 module toward the left so that it is no longer physically connected to the microPMU. 
 

 

 

Step 5: 
 

Reconnect input power to the microPMU device and download a copy of its current Setup.ini file via 
USB (see the microPMU Instruction Manual for details on downloading the setup file). 
 
The Setup.ini file must be manually edited with a text editor such as notepad. Copy and paste the below 

text into the bottom of the microPMU’s Setup.ini file and save the change

s to the file. 

 
;---------------------------------------------------- 
[SNTP_Settings] 
;---------------------------------------------------- 
Enable_SNTP=OFF 
SNTP_Server=2.pool.ntp.org 
; ------ Valid Values: 1 to 168 (1 week) 
SNTP_Update_Interval_In_Hours=1 
 
;---------------------------------------------------- 
[NTP_Settings] 
;---------------------------------------------------- 
Enable_NTP=OFF 
NTP_Server=north-america.pool.ntp.org 
; ------ Valid Values: 1 to 168 (1 week) 
NTP_Update_Interval_In_Hours=1 
 
 
 
 
 