background image

 

 

 

Two adjustable limit switches are installed to limit the stroke of the actuator, and cut-off the motor current in the 
relative direction. 

Most motors have a thermal switch, depending on the actuator type, to cut off the current in both directions when a 
maximum temperature is reached (only at standard single phase power supply). The thermal switch loop is closed by 
the bridge between the X5/6 and X5/7 connections (see Figure 3). 

7.2

 

Thermal switch as potential free contact 

The thermo switch can be wired to the outside as follows: 

 

Remove the bridge between connections X5/6 and X5/7. 

 

Change the connections X1/11 and X1/13. 

 

Check conductivity between connections X5/6 and X5/7 (connection must be there). 

 

Connect the thermo switch as potential free contact to the connections X5/6 and X5/7. 

 
Maximum thermal switch loading: 
The thermo switch can be loaded up to the maximum nominal value for the motor (see motor nameplate). 

 

When using the thermo switch as a potential-free contact, the switching signal must immediately 
stop the motor. Re-starting the motor is allowed only after the thermo switch has reset. Failure to 
observe this warning may result in damage to the actuator. 

 

 

8.

 

Valve mounting 

The PSR-E-C actuators are designed with a mechanical interface according to ISO 5211 for valve mounting. The gear 
contains a double square SW17 to connect the actuator to the valve shaft. 

 

Check that the actuator flange suits the valve flange. 

 

Use standard adapters to adapt to the valve shaft 

 

Clean the surface of the connection components, lubricate      

     valve shaft slightly 

 

Position the actuator on the valve. Tighten the screws in a  

      diagonal sequence according to the required torque. 
 

Pos. ①:  Actuator flange 

Pos. ②:  Drive bush 

 

Figure 6: Actuator flange 

 

 

 

 

 
① 

 
② 

 
① 

Summary of Contents for PSR-E Series

Page 1: ...Version 2019 08 08 2019 PS Automation GmbH Operating Instructions PSR E C ...

Page 2: ...afety regulations PSR E C actuators are built to state of the art technology and are safe to operate Despite this the actuators may be hazardous if operated by personnel that has not been sufficiently trained or at least instructed and if the actuators are handled improperly or not used as per specification This may cause danger to life and limb of the user or a third party damage the actuator and...

Page 3: ... after operation Danger of burning the skin Always observe the relevant operating instructions when fitting PS accessories or operating the actuator with PS accessories Connections for signal in and output are double isolated from circuits that can be under dangerous voltage 2 Usage as per specification The PSR E C quarter turn actuators are exclusively designed as electric valve actuators They ar...

Page 4: ...adjustment Depending on the operating time of the actuator the handwheel is either permanently engaged or it has to be pushed down against a spring for manual operation A sticker on the actuator cover indicates the relevant mode for manual operation At motor operation the handwheel serves as running indicator Electrical wiring is done to a terminal block under the actuator cover 5 Operating condit...

Page 5: ...d and secured against an accidental switching on Mains connection cables must be dimensioned suitably to accept the maximum current requirement of the actuator and correspond to IEC 227 and IEC 245 The yellow green coloured cables may be used only for connecting to earth When inserting cables through the cable connector ensure that the maximum bending radius for the cable is observed PSR E C elect...

Page 6: ...hood is valid for the specific actuator For any optional extras see the individual wiring diagram in the related service instructions X1 Internal wiring X2 Internal wiring X3 Internal wiring X4 Potentiometer 1 for PSAP X5 1 Neutral X5 2 Motor phase to open X5 4 Motor phase to close X5 6 Thermo switch as potential free contact X5 7 Thermo switch as potential free contact X6 Position signal switches...

Page 7: ...nnections X5 6 and X5 7 Maximum thermal switch loading The thermo switch can be loaded up to the maximum nominal value for the motor see motor nameplate When using the thermo switch as a potential free contact the switching signal must immediately stop the motor Re starting the motor is allowed only after the thermo switch has reset Failure to observe this warning may result in damage to the actua...

Page 8: ...crew Pos Stop screw Pos Protection cap Figure 7 Mechanical stop 10 Adjustment of limit switches Figure 8 Setting the switching cams for stroke limit switches The standard limit switches serve to switch off the motor when the end positions are reached Additional limit switches are free of voltage and serve to indicate the valve position These are available as optional auxiliaries The switches are a...

Page 9: ...necessary re adjust the limit switches 12 Maintenance The actuators are maintenance free if used under the operating conditions as stated in the data sheet The gearboxes are lubricated for lifetime and do not require further lubrication Caution During maintenance and repair the actuator must not be operated electrically 12 1 Cleaning The actuators should be cleaned dryly 12 2 Spare parts Defective...

Page 10: ... Signal Switches Gold 2WE Gold Positioner PSAP Position Transmitter PSPT Space Heating HR Potentiometer PD Increased Enclosure IP Increase to enclosure IP67 available With power supply 24 VAC the open motor phase can produce voltages up to 35 V due to motor generated induction voltage ...

Page 11: ...11 14 Declaration of conformity ...

Page 12: ... 66 Fax 91 20 25 47 39 66 E mail sales ps automation in www ps automation in Great Britain IMTEX Controls Ltd Unit 5A Valley Industries Hadlow Road GB Tonbridge Kent TN11 0AH Phone 44 0 17 32 85 03 60 Fax 44 0 17 32 85 21 33 E mail sales imtex controls com www imtex controls com Italy PS Automazione S r l Via Pennella 94 I 38057 Pergine Valsugana TN Phone 39 04 61 53 43 67 Fax 39 04 61 50 48 62 E ...

Reviews: