WARNING:
Ground fixture in accordance with local and national electrical codes. Failure to do so may result in serious personal injury.
6
5 of
LED
Bionic
| Recessed Linear
4˝ Slot
I N S T A L L A T I O N I N S T R U C T I O N S
CO N T IN U O U S R U N X 3, X 7
C 8 0 : C O R N E R S I N S T A L L A T I O N
1)
INSTALL C8O CORNER:
After removing reflectors and LED trays
but leaving shipping straps, install C8
corner in a wall with a 51/8˝ stud clearance.
Secure with screws through back of corner
into blocking between studs (by others).
3)
Confirm spacing at ends
of rows, ensuring that
there is enough room for
installation of finish trim.
INSTALL DRY WALL:
Install drywall, leaving a 5-1/8˝
opening for trim.
MINIMUM DISTANCES:
X3 Light Pocket = 3/4˝
X7 Light Pocket = 11/2˝
Wall-to-Wall = 1/2˝
DRY WALL
DRY WALL
2)
INSTALL ADJACENT SEC TIONS:
Continue installing straight sections
from the corner moving outward
according to row layouts in job drawing.
Pull sections together with aligner
joiner brackets, and secure to studs.
Pull electrical power into fixture.
ALIGNER
JOINER
BRACKET
5-1/8˝
4-11/16˝
Ceiling Fixture
C8I Corner
Wall Fixture
Studs
Studs
5-1/8˝
BLOCKING
5-1/8˝
5-1/8˝
07-02-2020