7 Controller 

functions

7.1 General controller functions

The controller compares the temperatures of the various measuring points and 
optimally charges the storage tank. If the collector temperature exceeds the 
storage tank temperature, the solar circuit pump is switched on. Monitoring and 
protection functions ensure safe operation.

7.1.1 Dual storage tank systems (diagram 1 and 2)

Examples of dual storage tank systems:

two separate storage tanks

one stratifi ed storage tank

one storage tank and a swimming pool, etc.

The controller detects the temperature changes in the collector and the storage 
media, determines the primary and secondary charging while, of course, taking 
into consideration the charging duration as well as an interruption of this func-
tion along with a waiting period to monitor the collector temperature. 

"Basic Setup" menu 

Display

 

Meaning

Value range Factory set-

ting

Line

Value

9

240

Controller response time in s

30 – 480

240

10

1

First-priority storage tank selection

1 – 2

1

7.1.2 RPM control

The A1 and A2 outputs can be operated using an RPM control.

"Programming" menu 

Display 

Meaning

Value range Typical set-

ting

min 
100 

 

12

Set the minimum pump capac-
ity using the RPM control 

100% = RPM control off 

30% – 100%

100%



 

Settings and changes in 
this menu must only be 

carried out by a specialised 
technician. Incorrect settings can 
damage or adversely aff ect the 
function of the solar power 
system.

 

Settings and changes in 
this menu must only be 

carried out by a specialised 
technician. Incorrect settings can 
damage or adversely aff ect the 
function of the solar power 
system.

Summary of Contents for SOLAREG II VISION plus

Page 1: ...Microcontroller controlled temperature difference controller for solar thermal systems Operatingmanual Operatingmanual Solareg II VISION plus...

Page 2: ...conditions 24 13 Declaration of conformity 24 The number of displayed values depends on the activated additional functions The number of displayed values depends on the activated additional functions...

Page 3: ...Real time clock function Available accessories Temperature sensor PT1000 Yield measurement set incl tube sensor Sensor connection box Immersion sleeves 2 Safety instructions Always completely disconne...

Page 4: ...Quick Info card provided with the device into the pocket provided on the back of the device The Quick Info card provides the user with an overview of the functions to facilitate rapid device operatio...

Page 5: ...cope 2 to 6 sensors are required Mounting wiring the temperature sensors Mount the sensors on the collector and the storage tank Ensure proper heat transfer and use heat conducting paste if necessary...

Page 6: ...Confirm a value change and store it 5 Menu structure 5 1 Info menu The following measured and yield values are displayed in the Info menu Display e g Meaning Can be reset 75 C Displays current collec...

Page 7: ...permis sible temperature 15 95 C 65 C dT max 7K Storage tank 1 2 Switch on differ ence 3 40K 7K dT min 3K Storage tank 1 2 Switch off differ ence 2 35K 3K min 100 12 Set the minimum pump capacity usi...

Page 8: ...n the Basic Setup menu Settings must only be changed by a specialised technician Settings may only be adjusted in the menu a within one minute after the device has been switched on or b after simultan...

Page 9: ...tank systems Controller response time in s 30 480 240 10 1 First priority storage tank selection 1 2 1 11 0 Anti freeze function 0 Off 1 On 0 12 6 Anti freeze function Reference sensor selec tion 1 6...

Page 10: ...onductor mains and outputs A1 Solar circuit pump switching output 1 A2 No function A3 Independent controller switching output 3 Sensor connections S1 Collector sensor S2 Lower storage tank S3 No funct...

Page 11: ...eter Type 1 one collector two storage tanks with a three way valve A2 Off The valve must es tablish the connection between the collector and storage tank 1 Type 1 one collector two storage tanks with...

Page 12: ...itching output 1 A2 Pump switching output 2 A3 Independent controller switching output 3 Sensor connections S1 Collector sensor S2 Lower storage tank 1 S3 Lower storage tank 2 S4 Collector return S5 O...

Page 13: ...ler other temperature display S7 Option flow meter Type 3 two collectors one storage tank with a three way valve The valve must es tablish the connection between collector 1 and the storage tank Type...

Page 14: ...outputs A1 Solar circuit pump 1 switching output 1 A2 Solar circuit pump 2 switching output 2 A3 Independent controller switching output 3 Sensor connections S1 Collector array 1 S2 Lower storage tan...

Page 15: ...n the charging duration as well as an interruption of this func tion along with a waiting period to monitor the collector temperature Basic Setup menu Display Meaning Value range Factory set ting Line...

Page 16: ...9 23 59 Heating If the measured temperature is below the target value output A3 is switched on until the measured temperature reaches the target value hysteresis Basic Setup menu Display Meaning Value...

Page 17: ...erature differ ence controller function can also be selected 0 Off 1 Cooling 2 Heat ing 3 Tem perature difference controller 0 15 5 Sensor selection for the independ ent controller source 1 6 5 Progra...

Page 18: ...only effective if the storage tank temperature is below the temperature limit 95 Therefore during the holiday period for example the storage tank is discharged at night to the set recooling temperatur...

Page 19: ...y yield measurement The energy yield of the solar power system is calculated and displayed using the temperature difference between the collector and the collector return tempera ture and the measured...

Page 20: ...d short circuits Errors are indicated by the symbol You can find the error source by scrolling up or down the Info menu 8 2 Flow monitoring The controller is programmed to display a message if the flo...

Page 21: ...ensor if necessary Flashing Short circuit in the sensor cable Check cable Defective sensor Check sensor resistance and replace sensor if necessary Circulation error No flowSFlb Flashing Additional dis...

Page 22: ...r Outputs are not switched on Controller is in manual operation Exit Manual operation Switch on condition is not satisfied Wait until switch on condition is satisfied Pump symbol rotates but the pump...

Page 23: ...ing output Total power of all outputs 230V 1A approx 230VA for cos 0 7 1 0 2A approx 460VA maximum Fuse protection Fine wire fuse 5 x 20mm 2A T 2 amperes delayed action fuse Miscellaneous Recommended...

Page 24: ...d within 1 month after PROZEDA GmbH has re ceived it If the device is not repaired within the two repairs attempts the buyer is entitled to delivery of a fully functional replacement product If a repl...

Reviews: