80EC
ELECTRICAL CONNECTION
Warning:
This boiler must be earthed.
All system components must be of an approved type.
Connection of the whole electrical system and any heating system controls to the electrical supply must be
through a common isolator.
Isolation should preferably be by a double pole switched fuse spur box having a minimum contact separation
of 3 mm on each pole. The fused spur box should be readily accessible and preferably adjacent to the boiler.
It should be identified as to its use.
A fused three pin plug and shuttered socket outlet may be used instead of the fused spur box, provided that:
a) They are not used in a room containing a bath or shower.
b) Both the plug and socket comply with the current issue of BS1363.
The mains electrical supply must be maintained at all times in order to provide domestic hot water and frost
protection.
It is recommended that a room thermostat is fitted.
Thermostatic radiator valves may be installed in addition to the room thermostat.
Note:
For further information, see The Building Regulations 1991 - Conservation of fuel and power - 1995
edition - Appendix G, table 4b.
DO NOT INTERRUPT THE MAINS SUPPLY TO THE BOILER WITH A TIME SWITCH OR PROGRAMMER.
The
Protherm 80EC
is delivered with 1metre mains supply lead ready connected.
The electrical supply cable is the original spare part and must be replaced only by original supply cable for
Protherm 80EC boiler.
External controls
The boiler will work for heating
AS DELIVERED
without a room thermostat fitted provided the two wires on
the integral external controls connection
REMAIN LINKED TOGETHER
(as supplied). If a room thermostat is
required, it must be connected as shown below and the link must be removed.
ANY ROOM THERMOSTAT USED MUST BE OF THE VOLTAGE FREE TYPE.
WARNING: ON NO ACCOUNT MUST ANY ELECTRICAL VOLTAGE BE APPLIED TO
EITHER OF THE TERMINALS OF THE EXTERNAL CONTROLS CONNECTION
WARNING:
This boiler must be wired in accordance with these instructions. Any fault arising from incorrect
wiring cannot be put right under the terms of the guarantee.
Diagram 12
Summary of Contents for 80EC
Page 2: ...Supplied By www heating spares co Tel 0161 620 6677 ...
Page 19: ...Supplied By www heating spares co Tel 0161 620 6677 17 80EC FLUE CONFIGURATIONS Diagram 1 1 ...
Page 31: ...Supplied By www heating spares co Tel 0161 620 6677 29 80EC ...
Page 32: ...Supplied By www heating spares co Tel 0161 620 6677 27 March 2001 ...