Protherm 20 KLO Instructions For Use And Installation Download Page 8

Supplied By www.heating spares.co  Tel. 0161 620 6677

3. Boiler Assembly 

3.1. General Rule 

PROTHERM KLO

 boiler can be put into operation only by an authorised installer. A network of the manufacturer's 

contractual service centres provides installation, maintenance and repairs. 

3.2. Connection to Gas Supply 

PROTHERM KLO – ZP 

types are designed for natural gas, with 1.8 kPa (18 mbar) pressure in the distribution network; the 

calorific value of natural gas is about 9 to 10 kWh/m

3

. The user's gas piping and gas meter must be sufficient for all gas 

appliances used on the premises. The pipe branch supplying the boiler must have the diameter corresponding to the boiler size, 
but a diameter one degree higher is recommended.  

PROTHERM KLO – P

 types are designed for LPG; the calorific value of natural gas is about 12.8 to 13 kWh/kg. Operation 

using cylinders would be problematic, due to both sufficient volume and handling of the cylinders; hence a prerequisite for the 
operation is an installation of an LPG tank near the heated premises and filling of the tank by an organisation authorised for such 
activities. 

Sufficient supply of LPG from the tank (and other gas appliances, if any) is part of the design and supply of the tank. For LPG 
boilers, a pressure-control valve must provide the pressure of exactly 3.0 kPa (30 mbar). 

3.3. Combustion Air Supply 

Stationary cast-iron 

PROTHERM KLO

 boilers take combustion air from the space – the air in the room must not contain dust or 

aggressive or flammable substances (vapours of glue, paint thinner, etc.) There must be the possibility of direct ventilation of the 
space, at a minimum volume of 0.8 m

3

 per each kW of the boiler's power output. If direct ventilation is impossible, the required 

volume is 2 m

3

 per each kW of power output. Direct ventilation is by ventilation openings to the outside air, or to neighbouring 

rooms that can be ventilated to the outside. Insufficient space is solved by ventilation openings of sufficient size.  

Gas appliances with flue gas removal to chimneys must not be in rooms in which negative air pressure is created by ventilation 
fans.  

3.4. Flue Gas Removal  

The boiler's flue gases are led to a chimney with continuous draft, at least 2 Pa. Connection to the chimney is by a flue-gas duct, 
whose diameter corresponds to the outlet on the boiler (depending on the boiler size). The duct is not included in the delivery. 

No elements reducing the draft (such as various exchangers for using the residual heat) are allowed to be inserted in the 
flue-gas duct.  

  

Installation of both the boiler and the flue-gas duct must comply with applicable standards. The standards' requirements prevent 
appearance of adversary effects, such as excessive cooling of the flue gases, penetration of chimney wall by humidity, and 
variability of chimney draft, which would affect the boiler operation in an undesirable manner. 

An extension, 

PROTHERM PT 20 (30, 40, 50) POLO – TURBO,

 can be used for forced removal of flue gases from 

PROTHERM 20, 30, 40, 50 KLO boilers. This makes it possible for the boilers (with the exception of the 

PROTHERM 60 KLO 

type) to be used on premises where a chimney cannot be used. The extension is directly connected to the boiler's flue-gas outlet. 
The extension fully replaces a chimney, for maximum length of the flue-gas duct up to 10 equivalent metres (1 equivalent metre: 
1 m of straight duct or one 90° elbow).  

Only authorised organisations may install the extension on a boiler and start its operation. Safety regulations and precautions must 
be adhered to when servicing the extension connected to the electric grid, even if switched off!  

3.5. Requirements for Heating Water Quality 

PROTHERM KLO

 boilers are designed for water pressure up to 400 kPa (4 bar).  

Water for filling and replenishment must be clear, colourless, without suspended solids, oil or chemically non-aggressive 
substances; the water mustn't be acidic (its pH must be above 7) and the carbonate hardness must be as low as possible.  

Sodium phosphate or chelating agent may be added to the water for filling. 

 

7

Summary of Contents for 20 KLO

Page 1: ...By www heating spares co Tel 0161 620 6677 Instructions for Use and Installation of Cast Iron Boilers PROTHERM 20 30 40 50 60 KLO BEAR Version Protherm s r o ltd Pplk Plju ta 45 909 01 Skalica Slovak...

Page 2: ...ig 3b Vertical Control Panel 11 Fig 4a Electric Wiring Diagram of PROTHERM 60 KLO 18 Fig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO 18 Fig 5a Regulation elements of SIT 843 combined gas ar...

Page 3: ...Do not remove or damage any labels or markings on the boiler 9 The boiler complies with all Czech applicable regulations If it is to be used in another country deviations in the regulations have to b...

Page 4: ...ted if the valve s motor is not active gets no voltage The boiler s manufacturer supplies both DHW reservoirs 100 150 200 l and suitable three way distribution valves l DHW heating takes preference ov...

Page 5: ...onnection Dimensions 1 Control panel 2 HCW pressure measuring point 3 HCW temperature measuring point 4 Boiler cast iron body 5 Combined gas armature 6 Water filling and discharging 7 Burner plate dis...

Page 6: ...the required and actual parameters i e the state of the boiler and the heating circuit the gas pipe leading out of the armature is part of the burner plate with 2 to 6 nozzles one per each burner tube...

Page 7: ...3 Chimney flange 4 Flue gas duct with draft dampener 5 SKKT chimney draft control system 6 Outgoing HCW 7 Gas supply 8 Cast iron elements 9 Incoming HCW 10 Combustion chamber 11 Secondary air supply 1...

Page 8: ...ce is solved by ventilation openings of sufficient size Gas appliances with flue gas removal to chimneys must not be in rooms in which negative air pressure is created by ventilation fans 3 4 Flue Gas...

Page 9: ...pes so that the pipe fixtures on the boiler should not be affected by any pressures or tensions The fixtures on the boiler have outside male threads l Closing valves are recommended to be installed on...

Page 10: ...gas piping i e electricity supply to the boiler must be stopped in addition to using the boiler switch e g by unplugging b Stopping the boiler whenever flammable or explosive vapours appear even if t...

Page 11: ...such defects may be caused by not igniting the flame no gas or the chimney draft control system if there is none or too low a draft or emergency thermostat if the HCW temperature is above 100 C may h...

Page 12: ...lements flue gas and emergency temperature thermostats disabled or replaced with elements different from those specified by the manufacturer Users are not allowed to tamper with the safety elements He...

Page 13: ...regulator If the boiler does not ignite and the defect indicator is off the operation is stopped due to one of the operational reasons we have just described the heating will automatically start agai...

Page 14: ...and persons under the influence of drugs or otherwise incapable must be prevented from operating the boiler 7 2 Quality Compliance The boiler s quality compliance is provided by and checked within the...

Page 15: ...olted on a palette Do not let any forces act on the casing when handling or when storing the boiler For handling without a palette the base can be used cf Chapter 2 For storage normal conditions have...

Page 16: ...eedle on the boiler pressure gauge 3 9 Electrical Connections of Boiler The electrical installation cabinet and the service part of the control panel are accessible when the top panel of the boiler is...

Page 17: ...nufacturer These elements must also be checked after each servicing on them 5 Boiler Operation 5 1 Boiler Preparation and Start Check water pressure on the boiler pressure gauge Turn the gas supply va...

Page 18: ...rocedure must be followed Only authorised service centres are allowed to carry out the conversion The following steps are to be followed 1 Dismount the burner from the boiler 2 Replace the nozzles wit...

Page 19: ...ig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO HV Main switch PO1 Electrical fuse SP Power stage switch TL1 RESET button DT1 Emergency state indicator HT Emergency temperature thermostat TS...

Page 20: ...1 620 6677 Fig 5a Regulation elements of SIT 843 combined gas armature for boilers 20 30 40 50 KLO a Input b Output 1 Setting screw for maximum 2 Setting screw for minimum Fig 5b Regulation elements o...

Page 21: ...2 3 Flue gas removal manner to chimney to chimney diam outlet mm 130 130 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 13 3 19 8 Effi...

Page 22: ...ue gas removal manner to chimney to chimney to chimney diam outlet mm 150 180 180 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 26 6 3...

Reviews: