FIRE CONTROL INPUT
The fire control input is an optically isolated input that
allows the output relays of the Protégé PGM Expander to
be deactivated in the case of an emergency. This input
must be activated by a voltage from 12-32VDC and it is
recommended that it is isolated from the access control
system.
The Protégé PGM Expander is designed for simple fire
control connection and this allows all of the Fire Control
terminals to be connected in parallel reducing the need
for external relays at each unit.
PGM OUTPUTS (1 to 16)
The 16 PGM Outputs each have a FORM C output relay
and an indicator showing the relay status. The
connection example below shows the control of an
external LED indicator from the auxiliary supply of the 16
PGM Output Expander.
Switching inductive loads that can produce
high back EMF voltages or large voltage
induced spikes can cause the 16 PGM Output
Expander to behave unexpectedly and should
be avoided. A suitable isolation circuit must
be installed between the relay contacts of the
16 PGM Output Expander and the inductive
load.
SPECIFICATION
Power Supply
DC Input Voltage
12VDC
(10.5VDC Min, 14.0VDC Max)
Operating Current
280mA (Typical)
~1.2A (All Relays Activated)
Communication
RS-485
Isolated Module Network
Outputs
16 Relay Form 'C'
7A, 250V (Max) Non Inductive
Loads Only
Status Output
50mA (Max) Open Collector
Inputs
Tamper Normally
Closed
Fire Control
12-32VDC (6-21mA)
Voltage Input
Button Inputs (Optional)
16 (Requires PRT-PX16-DRI
Interface)
Dimensions
PCB Dimensions
183mm X 234mm
7.2"
X
9.2"
Miscellaneous
Destination Reporting Yes (Optional Input Unit)
Fail Safe Operation
Yes (Configurable Option)
*Specifications are subject to change without notice, please
visit www.integratedcontroltechnology.com for the updated
information.
Unit C, 6 Ascension Place, Mairangi Bay, P.O. Box 302-340
North Harbour, Auckland, New Zealand.
Phone: +64 (9) 476 7124
y
Fax: +64 (9) 476 7128
www.integratedcontroltechnology.com
16 PGM Output Expander
Quick Start Guide
PRT-PX16
INTRODUCTION
The PRT-PX16 Protégé PGM Expander extends the
number of PGM outputs by 16. All 16 PGM Outputs
feature 7A FORM C High Current Relays with fire control
and power supply cut off integrated.
A true multiple function module the PRT-PX16 Protégé
PGM Expander can be connected to the slave
communication RS-485 interface of any PRT-RDI2 or PRT-
RDE2 PGM Expansion Module for simple cost effect
integrated elevator floor control with local autonomous
operation.
•
Secure Encrypted RS-485 Module Communications
•
16 High Current FORM C PGM Outputs
•
1 Open Collector Status Output
•
1.5A Switching Power Supply
•
Intelligent Battery Charge and Monitoring
•
Online and Remote upgradeable firmware
•
Optically Isolated Fire Control Input For Elevator
Systems
For a full installation manual or more information on the
Protégé PGM Expander and other Integrated Control
Technology products please login to our website
www.integratedcontroltechnology.com