FS2000 Series Fire Detection -
Preaction/Deluge Control Panel Operation
Installation Test and Maintenance
Operational Outline:
1. Normal Standby Condition
a) “AC ON” Indicator (Green) illuminated.
2. Power Supervision
AC power source failure:
a) “AC ON” Indicator (Green) OFF.
b) System trouble buzzer ON (Pulsing) - Press “SUP./TRO. SIL.” button to silence.
c) “SYS. TRO.” Indicator (Yellow) Flashing.
d) Restore AC power to resume standby condition.
DC power source failure:
a) “SYSTEM. TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “BATTERY OUT” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Restore DC power to resume standby condition.
3. Alarm Detection Circuits
Short in detection loop/device or fault = Alarm Condition:
a) “SYSTEM ALARM” Indicator (RED) ON.
b) “ZONE ALARM” Indicator (RED) ON.
c) All alarm notification appliance circuits activated. Press “AL. SIL.” button to silence, “AL. SIL.” Indicator (Yellow) Flashing.
d) Restore detection circuit or initiating device. Press “SYS. RST.” button to return to standby condition.
Open in detection loop - Zone Trouble/System Trouble:
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “ZONE TROUBLE” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP./TRO. SIL.” button to silence.
d) Clear detection circuit to return to standby condition.
4. Notification Appliance Circuits
Short in notification appliance circuit loop - Al. Short:
a) “SYSTEM TROUBLE / SUP” Indicator (Yellow) Flashing.
b) “ALARM SHORT” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Clear (repair) short to circuit to return to standby condition.
Open in notification Appliance circuit loop - Al. Open:
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “ALARM OPEN” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Clear (repair) open to circuit to return to standby condition.
5. Switch Supervisory Zone
Short in switch supervisory circuit - Supervisory Alarm/System Trouble:
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) steady.
b) “ZONE ALARM” Indicator (Yellow) ON.
c) System trouble buzzer ON (Steady) - Press “SUP. / TRO. SIL.” button to silence. System is now ready for subsequent
supervisory alarm i.e., next supervisory alarm condition will reinstate system supervisory alarm condition.
d) Press “SUP. / TRO. SIL.” button to silence.
e) Restore supervisory circuit or initiating device. Press “SYS. RST.” button to return to standby condition.
Open in switch supervisory circuit - Supervisory Trouble/System Trouble:
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “ZONE TROUBLE” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Repair open to return to standby condition.