CirrusPro User Manual
4.0 Fault Finding
Internal diagnostics monitor for faults that may normal running.
4.1
Fault List
The list below shows all the possible faults and their codes:
1 Processor fault
2 Corrupt eeprom
3 Supply fault
4 No water
5 Chamber seal
6 Vacuum fault
7 LED fault
8 Water fill fault
9 Airflow fault
10 Stack overflow
11 Unit isolated
12 Low supply voltage
13 Algotec fault
14 Unit cold Fault
15 Unit disabled
16 Expansion board fault
17 External fault
18 Battery Fault
19 Mains Fault
20 Sample blocked
21 Purge blocked
22 Zone Override Enabled
The numbers correspond to the Fault Codes, which can be extracted as described below.
4.2
Indicating Fault Codes on the Detector Unit
The CirrusPro can pulse the Fault LED to indicate fault code of current Faults or the last fault if there
are no current Faults.
When the unit is in Fault, press and
hold
the Silence button.
The Fault LED will illuminate for 5 seconds, then pulse a number of times indicating the fault code.
When the code is complete, the Fault LED will illuminate for 5 seconds.
The code will repeat or further fault codes will be indicated.
Faults are indicated in numeric order i.e. Code 3 before Code 4 etc.
Fault LED indicating one fault (fault code 4 – No water).
Fault LED indicating two fault codes (fault codes 3 & 4).
The sequence will repeat until the Silence Button is released.