Protec Cirrus Pro 100 User Manual And Responsibilities Download Page 12

 

 

93-523-23 Issue 4               

Page 12 of 21                 

CirrusPro User Manual 

 

Inspect and clean if necessary airflow thermistor. The thermistor can be seen from the top of the 
manifold. 
 
 
 
 
 
 
 
 
 
 
IMPORTANT: Ensure the unit is switched off.  
Use a small brush to brush away any accumulated dust particles. 
Be careful not to move the alignment of the thermistor. The thermistor must be aligned central to 
the hole in the correct orientation, refer to the diagrams above.   

 
 

Summary of Contents for Cirrus Pro 100

Page 1: ...rotec Fire Detection Export Ltd Protec House Churchill Way Nelson Lancashire BB9 6RT Telephone 44 0 1282 717171 Fax 44 0 1282 717273 CIRRUS PRO ASPIRATING FIRE DETECTOR User Manual and Responsibilitie...

Page 2: ...should be made to Protec Fire Detection Export Ltd in writing within 12 months from date of delivery This Warranty shall not apply to a detector which has been 1 subject to misuse negligence or accide...

Page 3: ...ser Manual Issue Date Author 1 First Issue 26 04 05 jlh 2 Minor Changes Display Software v1 09 02 06 05 jlh 3 1 UL Information introduced 14 02 06 sb 3 2 4 References to Bellows removed Airflow thermi...

Page 4: ...Periodic Checks 11 2 1 1 Daily Checks 11 2 1 2 Three monthly Checks 11 2 1 3 Annual Checks 11 3 0 USER GUIDE 13 3 1 Front Panel Indications and Controls 13 3 2 Panel Display 13 3 2 1 Main Options Menu...

Page 5: ...nses onto the small particles and forms a cloud Consequently the thermally generated particles cause many droplets to form into the cloud which is then detected by the measuring system of the Cloud Ch...

Page 6: ...inlet ports CirrusPro 200D As CirrusPro 200 with built in Display Panel See CirrusPro RDP CirrusPro 200DSC As CirrusPro 200D but with four scanned sampling pipe inlet ports CirrusPro 200 no display 2...

Page 7: ...Coverage Per Sample Head or Point 30 x 30 9 144m x 9 144m Number of Zones Pro 100 1 Zone Pro 200 1 Zone Pro 200 1 Zone Pro 200D 1 Zone Pro 200D 1 Zone Pro 200DSC Field Programmable up to 4 Zones Pro 2...

Page 8: ...high ambient temperature 30C conditions will increase the water usage Unit Operating Temperature 32 100 F 0 37 8 C ambient Relative Humidity 0 95 non condensing ambient Cabinet Pro 100 11 22 x 8 47 x...

Page 9: ...48 Minimum Number of Sampling Heads or Points 2 per Zone Alarm Thresholds 4 per Zone Sampling Manifolds Minimum 2 per zone Maximum 12 per zone Zone Manifold 1 per Zone Sampling System DT Transport Tim...

Page 10: ...ons will increase the water usage Unit Operating Temperature 32 100 F 0 37 8 C ambient Relative Humidity 0 95 non condensing ambient Cabinet 17 32 x 15 15 x 5 51 440mm x 385mm x 140mm Air Sampling Sys...

Page 11: ...the extent of the fault and decide whether special actions such as fire patrols are needed Check that any fault reported previously has been attended to 2 1 2 Three monthly Checks The following must b...

Page 12: ...istor can be seen from the top of the manifold IMPORTANT Ensure the unit is switched off Use a small brush to brush away any accumulated dust particles Be careful not to move the alignment of the ther...

Page 13: ...n the power is present but flashes when a remote power supply fault is detected If the power indicator is off there is no power to the unit Controls Silence Releases the activated alarm relays and or...

Page 14: ...status and displays the following depending on model Showing the current particle levels for the sample pipes Pressing Menu requires a password Use the and to select the number and press Enter The low...

Page 15: ...ns available on the menus Select Changes highlighted value or moves to a further menu and Increase and decrease the highlighted value Accept Stores changes in the detector unit when necessary Some cha...

Page 16: ...89 ABCDEFGHIJKLMNOPQRSTUVWXYZ _ abcdefghijklmnopqrstuvwxyz After editing as required press Exit to return to the Unit Pipe Text display Press Accept when all the text has been modified to send the tex...

Page 17: ...ependent on what has happened during the recording period The amount of data stored increases during fire and pre alarm events 3 2 6 Security Code On opening this screen the display shows 0 Use and to...

Page 18: ...changing the code Record the User Security code here User Code 3 2 7 Service Information Acceptable Values Pump Pressure 5 7 psi Supply voltage 19V to 30V LED current is 0 26mA to 5 67mA Airflow Refer...

Page 19: ...bled The numbers correspond to the Fault Codes which can be extracted as described below 4 2 Indicating Fault Codes on the Detector Unit The CirrusPro can pulse the Fault LED to indicate fault code of...

Page 20: ...feature Open circuit voltage 16V Max applied voltage 30V Max closed circuit resistance 1500 Ohms Output Relays 4 Programmable Fire Relays 1 Fault Relay 4 Additional Pipe on the expansion board for sam...

Page 21: ...User Manual Cirrus Pro Series Aspirating Fire Detectors Worldwide Manufacturer PROTEC FIRE DETECTION EXPORT LIMITED Protec House Phone 44 1282 717171 Churchill Way Fax 44 1282 717273 Nelson E mail sal...

Reviews: