Protec AC-200A Manual Download Page 11

                                                                                                             

AC-200A A/C System Maintenance Centre 

 

10) Usage of the Auxiliary Port 

A

 

Leak checking by N2 

i.

 

Remove the cap of auxiliary port after the equipment stop working entirely. 

ii.

 

Connect the N

2

 to the auxiliary port.   

Note: the connector to the auxiliary port must be with thimble. Do not open the valve 

of N

during this process. 

iii.

 

Adjust the N

2

 pressure to a suitable value and open the valve of N

2

. When the pressure is 

stable, please close the valve of N

2

. Normally, the pressure is adjusted to about 12~15bar. 

iv.

 

Check if there has any leakage in the A/C system. After checking, please press the needle in 

the auxiliary port to relive the N

2

v.

 

After finished, re-back the cap to the auxiliary port. 

B

 

Recharging from cans 

i.

 

Before vacuum, connect the pipe with the external tank to the auxiliary port. 

Note: the connector to the auxiliary port must be with thimble. Do not open the valve 

of external tank

 

during this process.

 

ii.

 

Run vacuum function. 

iii.

 

Open the valve of  external  tank to recharge the right amount refrigerant into  A/C system. 

And then close the valve of external tank. 

iv.

 

After finished, disconnect the pipes and re-back the cap to the auxiliary port. 

11) Maintenance 

A

 

Calibration of load cell

 

When the load cell is not precise

,

 it needs to be calibrated. 

Calibrating procedure as below: 

i.

 

Prepare a 15 kg weight. And remove the refrigerant tank from scale pan and keep the 
pan empty. 

Note: do not disconnect the red and blue hose from the refrigerant tank. It’s better 
put the refrigerant tank on a lower stage

ii.

 

Press and hold “STOP” key then power on the equipment. Press”+”or ”-” to select the 
load cell of cleaning tank (internal tank, SEN1) or of the recharging tank (external tank, 
SEN2). Press “ENTER” key to the calibration process. 

iii.

 

The LED displays “1” in flushing. 

iv.

 

Press "ENTER" key to do the empty plan calibration. Then the LED will  display “2”  in 
flushing. 

Note: If LED shows “ERR1”

please refer to the APPENDIX: ALARM CODE 

TABLE

v.

 

Put the 15 kg weight onto the scale pan and press “ENTER” key. Then LED displays the 
weight value and adjusts the value to 15 by press “+” or “-”key.     

Note: if the weight is 20kg, the value must be set to 20. 

vi.

 

Press “ENTER” key to do the scale linear calibration. Then the LED displays “END” to 
mean it’s successful for the calibration. 

Note: if LED shows “ERR2”, please refer to the APPENDIX: ALARM CODE TABLE. 

Summary of Contents for AC-200A

Page 1: ...AC 200AA C System Maintenance Centre AC 200A A C System Maintenance Centre...

Page 2: ...of the machine Keep away from moving parts and rotating elements such as cooling fans alternators and heating components etc to avoid harm Wear protective clothing gloves and goggles As automotive air...

Page 3: ...y functions 2 3 Operation 3 1 Parts descriptions 3 2 First use 4 3 Recovery Recycling 4 4 Preparations before Flushing 5 5 Flushing Recovery 5 6 Vacuum 6 7 New oil adding 6 8 Recharging 6 9 Refrigeran...

Page 4: ...easy and fouling to restore the A C system performance B With forward flushing reverse flushing and pulse flushing functions which greatly improve the cleaning effect C Using large size glass tube wit...

Page 5: ...Recovery Recycling C Used oil discharging D Vacuum E New oil filling F Recharging 2 Subsidiary functions A Refrigerant supplying B Load cell calibration C Recharging tank exchanging procedure D Mainte...

Page 6: ...il adding New oil bottle Parameter decrease key Parameter increase key Enter key Flushing key Min indicator Kg indicator LED displayer Recovery key Filling key Start key Switch for used oil discharge...

Page 7: ...ank 2nd Open the valve of the refrigerant tank and place it upside down on the load cell pan 3rd Fix it with the accessories Note If you need not using the auxiliary load cell please fix it as the man...

Page 8: ...ocess Otherwise it easily causes damages to the air conditioning and risk of accident C Press key to select the Recovery Flushing function D The LED displays the flushing time E Set the flushing time...

Page 9: ...ys code as F00 during the process please refer to the APPENDIX ALARM CODE TABLE 7 New oil adding A Pour new oil into the new oil bottle Note add new oil more 20ml than the used oil drained out to avoi...

Page 10: ...is kg D Presses START key to run E Stop automatically after recharging finished Note In the filling process if LED displays alternately the remaining amount of filling and the letters AC it means tha...

Page 11: ...of external tank iv After finished disconnect the pipes and re back the cap to the auxiliary port 11 Maintenance A Calibration of load cell When the load cell is not precise it needs to be calibrated...

Page 12: ...the LED displays F008 the vacuum pump oil must be changed ii Step 1 unscrew the block of the drain port to drain entirely out the old oil Then re back the block to the drain port iii Step 2 unscrew th...

Page 13: ...ory C 2 Set the recharging tank external tank as default viii Press ENTER to save ix Power off B Parameter inquiring i Press and hold Recharging key to enter parameter inquiring mode ii In this mode f...

Page 14: ...lue according to the ID pasted on the dry filter Only you set the correct 4 digits the equipment can accept it Note The code used already will be not able to be accepted again vi Code CON total times...

Page 15: ...06 Exchange dry filter The dry filter is life end F007 Vacuum pump maintenance Change the pump oil in time F009 No enough refrigerant in recharging tank Change a new tank of refrigerant F010 Prohibit...

Reviews: