18
Technical data
Display
16 LEDs for voltage (12, 24, 48, 120, 230, 400, 690 and 1000 V), polarity ( + ~ - ),
continuity (Rx/
) and phase/rotating field (R / L), FI + ELV
Rated voltage range
6...1000 V AC
6…1400 V DC
Phase sequence indication
Yes
Indication
0.85 Un
Frequency range
0, 16.66...500 Hz
Switchable load
30 mA at 230 V AC
Duty cycle
30 s on \ 240 s off
Nominal In current
< 3.5 mA
Peak current Is
< 0.3 A, with buttons pressed (FI/RCD)
Phase test Pol
> 100 V AC
Protection class
II
Impedance
625 k
for ELV AC
Continuity test
0...200 k
Climate category
N Normal
Operating temperature
-15 to +45 °C, at > 95% RH to +31 °C
Protection class
IP 65
Overvoltage category
CAT IV 1000 V
Testing standard
EN 61243-3:2014
Voltage supply
2x 1.5 V Type AAA Micro