6201-WA-MNET
♦
ProLinx Wireless
Configure the MNET Client Module
High Speed Wireless Modbus TCP/IP Gateway
Page 18 of 48
ProSoft Technology, Inc.
June 27, 2007
Consumer Command Narrative for the First Command:
Consume data using Unicast Mode.
1
Consume this data only from IP Address 172.16.10.131.
2
Consume 600 words and store them beginning at DB register 0.
3
Do not use a Swap Code.
4
Consume data within 400 milliseconds.
5
Only consume data with an Exchange ID of 1000.
The second line does exactly the same thing for another 600 words. However it
consumes this data into database registers beginning a register 600 and uses an
Exchange ID of 1001.
In order for these commands to work, the 6201-WA-MNET (to be configured as
the Server module) must also be configured to consume data being produced by
the 6201-WA-MNET (configured as a Client) into the appropriate database
registers and as well as be set up to produce data to allow the MNET Client to
consume. Setting up the corresponding MNET Server configuration is discussed
later in this guide.
Note:
The sample configuration file also shows an additional Produce and
Consume command. These commands are designed to pass a time value
from the MNET Client to the MNET Server module and then loop back from
the MNET Server to the MNET Client. These commands are included for
testing and radio communication verification purposes only and are not
necessarily required for your application.
How it's Done
1
Double-click on the
icon.
2
Click the Add button. ProSoft Configuration Builder adds a default row.