MVI56E-MCMR ♦ ControlLogix Platform
Start Here
Modbus Communication Module with Reduced Data Block
User Manual
ProSoft Technology, Inc.
Page 31 of 223
Adding Multiple Modules (Optional)
Important: If your application requires more than one MVI56E-MCMR module in the same project,
follow the steps below.
1
In the
I/O
C
ONFIGURATION
folder, click the right mouse button to open a
shortcut menu, and then choose
N
EW
M
ODULE
.
2
Select
1756-MODULE
3
Fill the module properties as follows:
Parameter
Value
Name
Enter a module identification string. The recommended value is
MCMR_2. You will need to link this name with the MSG paths for
the AOI.
Description
Enter a description for the module. Example: Modbus
Communication Module with Reduced Data Block
Comm Format
Select
D
ATA
-INT
(Very Important)
Slot
Enter the slot number in the rack where the MVI56E-MCMR
module is located.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly
Instance
4
Configuration Size
0