MVI56E-MCMR ♦ ControlLogix Platform
Diagnostics and Troubleshooting
Modbus Communication Module with Reduced Data Block
User Manual
ProSoft Technology, Inc.
Page 123 of 223
Operation Messages
After the initialization step, the following message pattern will be repeated.
<Backplane Status> <IP Address> <Backplane Status> <Port Status>
Code
Message
<Backplane Status>
OK: Module is communicating with processor
ERR: Module is unable to communicate with processor. For
this scenario, the <Port Status> message above is replaced
with "Processor faulted or is in program mode".
<IP Address>
Module IP address
<Port Status>
OK: Port is communicating without error
Master/Slave Communication Errors: port is having
communication errors. Refer to PCB diagnostics (page 120,
page 128) for further information about the error.
5.1.2 Non-Scrolling LED Status Indicators
The non-
scrolling LEDs indicate the module’s operating status as follows:
LED Label
Color
Status
Indication
APP
Red or
Green
OFF
The module is not receiving adequate power or is not securely
plugged into the rack. May also be OFF during configuration
download.
GREEN
The MVI56E-MCMR is working normally.
RED
The most common cause is that the module has detected a
communication error during operation of an application port.
The following conditions may also cause a RED LED:
The firmware is initializing during startup
The firmware detects an on-board hardware problem
during startup
Failure of application port hardware during startup
The module is shutting down
The module is rebooting due to a ColdBoot or WarmBoot
request from the ladder logic or Debug Menu
OK
Red or
Green
OFF
The module is not receiving adequate power or is not securely
plugged into the rack.
GREEN
The module is operating normally.
RED
The module has detected an internal error or is being
initialized. If the LED remains RED for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.
ERR
Red
OFF
The battery voltage is OK and functioning.
ON
The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If ERR LED still does not go off, contact ProSoft
Technology, as the battery is not a user-serviceable item.