In the
New Module
dialog, enter the
Name
,
Description
, and
Slot
options for
your application, then click on the
Connection
tab.
Parameter
Value
N
AME
MVI56E_GEC
D
ESCRIPTION
Enter a description for the module. Example: Generic ASCII
Ethernet Communication Module
C
OMM
F
ORMAT
Select
D
ATA
-INT
S
LOT
Enter the slot number in the rack where the MVI56E-GEC
module is located
I
NPUT
A
SSEMBLY
I
NSTANCE
1
I
NPUT
S
IZE
250
O
UTPUT
A
SSEMBLY
I
NSTANCE
2
O
UTPUT
S
IZE
248
C
ONFIGURATION
A
SSEMBLY
I
NSTANCE
4
C
ONFIGURATION
S
IZE
0