PS69-DPS
♦
CompactLogix or MicroLogix Platform
Reference
Profibus DP Slave Communication Module
Page 50 of 94
ProSoft Technology, Inc.
January 12, 2009
5.1.2 Hardware
Specifications
Specification Description
Processor
EC1-160P with integrated ASPC2
PROFIBUS Interface
RS-485, max. 12 MBaud, potential free, according EN 50170
Diagnostic Interface
RS232, PS/2 Mini DIN female connector, 9600 Baud, non isolated
Power Supply
+5 V ±5 % / 260 mA
Max. Distance Rating
max. 6 modules to the power supply module
Dimensions
Standard 1769 Single-slot module
Burst
EN 61000-4-4, 2 kV, 5 kHz
Surge
EN 61000-4-5, 2 kV common mode, 1 kV differential mode
ESD
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Radiated/ Conducted
Immunity
EN 61000-4-3, 10 V/m, 30...1000 MHz, 80% AM, 1 kHz sinewave
EN 61000-4-6, 10 V, 0,15...30 MHz
Radiated/ Conducted
Emission
EN 55011 Class A
Vibration/Shock
IEC 600068-2-6, 10-150 Hz, ± 0,75 mm, ± 1 g, 1 Octave/min
IEC 600068-2-27, 15 g, 11 ms
Operating Temp.
0 to 60°C (32 to 140°F)
Relative Humidity
5 to 95% (non-condensing)
Agency Certification: UL/CE
C-UL certified, UL 508 listed, CE
PROFIBUS conformance
certified
5.1.3 Functional
Specifications
Specification Description
Input data
max. 244 Bytes
Output data
max. 244 Bytes
DPV1 services
Read / Write class 1, Alarm
GSD file
PSFT097A.gsd
Up to 32 PROFIBUS devices can be connected to one bus segment. If several
bus segments are linked to each other with repeaters, there can be up to 127
devices on the network.
The maximum length of a bus segment depends on the baud rate used. Only
PROFIBUS certified cable, preferably Belden 3079A cable (or equivalent), should
be used.
Baud rate in kBit/s
Max. Distance
9.6
1,200 m / 4000 ft
19.2
1,200 m / 4000 ft
93.75
1,200 m / 4000 ft
187.5
1,000 m / 3280 ft
500
400 m / 1300 ft
1,500
200 m / 650 ft
3,000
100 m / 325 ft