Operation
Page 36 of 83
Ensure that all application code making use of slave device data first
checks that the DataExchangeActive bit is 1.
IdentMismatch
The device configured in the PLX50 Configuration Utility and the
device at the configured node address do not match because they
have different ident numbers.
1 – Online device Ident does not match configured device
0 – Online device and configured device ident match
DisabledByOutputAssembly
This bit indicates if the device has not been enabled for data exchange
in the PLX51-PBS device enable control bits.
1 – Device has not been enabled for data exchange
0 – Device has been enabled for data exchange
DeviceError
This bit indicates an error with the device.
1 – Device has an error
0 – Device has no error
The error flag will be set when one of the following conditions occur:
If there is an ident mismatch during slave parameterization.
When receiving any form of FDL fault (data link layer fault). For
example: SAP Not Activated or Resource Not Available.
When the data size of the DPV0 data exchange does not match
what has been configured in the PLX50 Configuration Utility.
This Error flag is transient and will clear once a valid response is
received.
AlarmPending
Indicates the device has an alarm pending on the PROFIBUS network.
When the bit is set ‘1’, the device has an alarm pending that must be
unloaded.
When the bit is set ‘0’, the device does not have an alarm pending.
0 – The node has no alarm pending
1 – The node has an alarm pending
DiagnosticsPending
Indicates the device has diagnostics pending on the local PROFIBUS
network.
When the bit is set ‘1’, the device has diagnostics pending that must
be unloaded.
When the bit is set ‘0’, the device does not have any diagnostics
pending.
0 – The node has no diagnostics pending
1 – The node has diagnostics pending
OutputAssemblyNodeAddrMismatch Indicates that there is a mismatch between the actual device station
address and the expected Logix mapping station address.
0 – Station address matches
1 – Station address mismatch
MappingCRCMismatch
If there is a mismatch in the mapping between Logix and the PLX51-
PBS, it can result in data appearing in the incorrect location. This
means you can be sending incorrect data to a device which can have
unpredicted results.
Summary of Contents for PLX51-PBS
Page 1: ...PLX51 PBS PROFIBUS DP Slave to EtherNet IP Gateway August 29 2019 v1 0 USER MANUAL...
Page 2: ...Page 2 of 83...
Page 5: ...Page 5 of 83 Warranty Information 81 11 Index 83...
Page 6: ...Page 6 of 83...
Page 10: ...Page 10 of 83...
Page 72: ...Page 72 of 83...
Page 78: ...Page 78 of 83...
Page 82: ...Page 82 of 83...