3.2.3 Using the Data Analyzer (Serial Protocols Only)
The Data Analyzer is an extremely valuable troubleshooting tool available in
PCB. It allows you to
“see” the data packets entering and leaving the serial ports
on the gateway. You can also capture this data to a log file.
Note:
The PCB Data Analyzer is for serial ports only. To analyze data traffic on an Ethernet port,
we recommend using a network protocol analyzer available on the Internet, such as Wireshark.
To use the Data Analyzer
6
Open the
Diagnostics
window in PCB.
7
On the toolbar at the top of the window, click the
Setup Data Analyzer
button.
8
In the
Data Analyzer Setup
dialog box, specify the time tick interval, the serial
port number, and whether the data packet contents should be displayed in
hexadecimal number or ASCII character format. Click
OK
.
Note:
The time tick is a symbol (_TT_) displayed on the Data Analyzer screen that allows you to
estimate time intervals during a Data Analyzer session. The time tick will print at the time interval
you specify in the
Data Analyzer Setup
dialog box. For example, if you select 10 mS Ticks, it will
print every 10 milliseconds.