MVI56E-LDM-MQTT ♦ MQ Telemetry Transport
Connecting to the MVI56E-LDM Module
ControlLogix® Platform
Quick Start Guide
ProSoft Technology, Inc.
Page 13 of 55
3.2.1 Firmware Update
1
Obtain the .firmware file from the MVI56E-LDM-MQTT zip file, or that was built in
the “Creating a Build” section in this document.
2
Download the .firmware file to the module via the module’s webpage. Refer to
the MVI56E-LDM Developer Manual for details.
Figure 3:
Firmware Update Page
3
At the end of the Firmware Update process, the module reboots and connections
to the module are lost during reboot.
4
The sample application starts running automatically after reboot. It still needs to
be configured.