PC56
♦
ControlLogix Platform
Installing the PC56 Embedded PC
In-Rack Industrial PC
Quick Start Guide
Page 16 of 25
ProSoft Technology, Inc.
November 18, 2009
RS-485 Application Port(s)
The RS-485 interface requires a single two or three wire cable. The Common
connection is optional and dependent on the RS-485 network. The cable required
for this interface is shown below:
Note:
Terminating resistors are generally not required on the RS-485 network, unless you are
experiencing communication problems that can be attributed to signal echoes or reflections. In this
case, install a 120-ohm terminating resistor on the RS-485 line.
RS-485 and RS-422 Tip
If communication in the RS-422/RS-485 mode does not work at first, despite all
attempts, try switching termination polarities. Some manufacturers int/-
and A/B polarities differently.
DB9 to RJ45 Adaptor (Cable 14)