MVI56-DH485R
♦
ControlLogix Platform
Ladder Logic
DH485 Interface Module for Remote Chassis
User Manual
Page 40 of 97
ProSoft Technology, Inc.
August 27, 2009
2 Edit the Module Properties.
Select the
R
EQUESTED
P
ACKET
I
NTERVAL
value
for scanning the I/O on the module. This value represents the minimum
frequency that the module will handle scheduled events. This value should
not be set to less than 1 millisecond. The default value is 5 milliseconds.
Values between 1 and 10 milliseconds should work with most applications.
3
Save the module. Click
OK
to dismiss the dialog box. The
C
ONTROLLER
O
RGANIZATION
window now displays the module's presence.
4
Copy the Controller Tags from the sample program.
5
Copy the User Defined Data Types from the sample program.
6
Copy the Ladder Rungs from the sample program.
7
Save and Download (page 15) the new application to the controller and place
the processor in run mode.