User Parameter Message, Full Format
Name Value
Description
Octet 51:
00h
Slot 8 all sizes zero
Octet 52 to 244:
00h
Not used
1
In your network, double-click on the slave icon.
You see the 3170-PDP Device Parameters screen
Double-click on
You see the User Parameter Data screen:
2
Enter the Full Format data values as shown in the User Parameter example:
User Parameter Example
User Parameter Message, Full Format (Length 43 bytes)
Name Value
Description
Octet 8
00h
Reserved
Octet 9:
0Bh
Full Format, Use safe state
Octet 10 to 11:
0281h
Slot 1 Module Key 1794-IB16 16-point discrete input module
Octet 12:
10h
Slot 1 config size 1 word, safe state size 0 words
Octet 13 to 14:
0000h
1 config word, input delay times
Octet 15 to 16:
0191h
Slot 2 Module Key 1794-OB16 16-point discrete output
module
Octet 17:
01h
Slot 2 config size 0 words, safe state size 1 word
Octet 18 to 19:
0000h
1 safe state data word, safe state value for output points
Octet 20 to 21:
1920h
Slot 3 Module Key 1794-IE8 8-point analog input module
Octet 22:
10h
Slot 3 config size 1 word, safe state size 0 words
Octet 23 to 24:
0000h
1 config word, channel selection
Octet 25 to 26:
5121h
Slot 4 Module Key 1794-OE4 4-point analog output module
Octet 27:
24h
Slot 4 config size 2 words, safe state size 4 words
Octet 28 to 29:
0000h
2 config words – channel selection and
output enable
Octet 30 to 31:
0000h