![Prosense S-DP32 User Manual Download Page 12](http://html1.mh-extra.com/html/prosense/s-dp32/s-dp32_user-manual_1618711012.webp)
12
PRS-UM-DP32-EN-Rev.02-05.2019
Main Board and Connections
S-DP32 Control panel has one integrated main board. All components and connections are
located on main board.
Main Board Details:
S-DP32 Control panel has all connections on main board.
Diagram 11: Control panel main board
As shown in the picture, there is a 3V battery on the panel electronic board to keep data and
time information. It may operate during the normal lifetime of the control panel. It should
be replaced when it is run off.
There are five sockets on the main board to install optional relay modules. Each relay
module has 8 relay on it and each relay controlled by one detector. It is also possible to take
an independent output from each relay (each detector). The relay module install location
should be used as follows:
1. Zone (1. Bölge): Alarm relay for detectors 1-8
2. Zone (2. Bölge): Alarm relay for detectors 9-16
3. Zone (3. Bölge): Alarm relay for detectors 17-24
4. Zone (4. Bölge): Alarm relay for detectors 24-32
5. Zone (5. Bölge): Not in use
LCD brightness adjustment potentiometer
Relay module mounting holes
Main power
input
Backup
battery input
Clock battery
Digital input
Relays and relay outputs
Buzzer
Relay test buttons
RS485 input
Power output
for detectors