Press up and down arrow buttons to see other detectors. If the detector is not installed screen will 
show not installed status with detector number: 

 

 

 

Press T button to return back to main menu. Menu will return to display mode if user not take any 
action for a minute. 

7. ALARM STATUS 

There are 4 independent LEDs for each zone module as fault, alarm, fan1 and fan2. Depending of the 
alarm activation type PPS Manager activate Fan1, Fan2 or Alarm relays and activate related LEDs on 
the front panel. As  it is designed to work for parking areas, fan1 will be activated to start ventilation 
when average or any one of the detectors gas reading reaches the defined level. Then if gas 
measurement still increasing the Fan2 relay will be activated. Finally if the measured gas level 
reaches the alarm level the alarm relay will be activated.  
 
In additition to these zone module relays there are one fault and one alarm relay on main pozer 
control board to monitor overal status. The fault relay will be activated any one of the zone module 
raises a fault condition. Same as fault, alarm relay will be activated any one of the zone module raises 
an alarm condition.  The LEDs and related relay outputs will be active untill detector  change the 
alarm status.  

7.1 What to do in case of alarm 

Refer to the mandatory safety procedures (gas alarm) set forth by your safety manager. 
Recommendations: 
Keep calm and follow these instructions: 

1.

 

Put out all naked flames (including cigarettes, pipes, etc.) 

2.

 

Turn off all gas appliances. 

3.

 

Turn off the gas supply at the tap and/or on the gas bottle (in the case of LPG). 

4.

 

Do not switch electrical appliances, lamps or the gas detection control unit on or off. 

5.

 

Open all windows and doors to air the room. 

6.

 

Do not “reset” the control unit if it is in the same room. 

If the gas concentration reading on the control unit does not fall below the level of alarm, and the 
reason for the gas leak is not immediately apparent and/or cannot be repaired, quit the premises 
and call the gas supplier and/or emergency services immediately to check the installations and to 
make the premises safe and to possibly carry out the necessary repairs. 

D01 Wrkg 
CO  000P 

D12 

Not Ins. 

Summary of Contents for PPS Manager

Page 1: ...EN Rev 03 10 04 2020 PROSENSE PPS Manager Gas Control Panel User Manual Prosense Teknoloji San Ltd ti Cumhuriyet Mah Mermer sok No 16 Kartal stanbul Tel 90 216 306 77 88 Faks 90 216 473 81 29 www pro...

Page 2: ...who rely on this product for their safety could suffer severe personel injury or death Properly installed panel can be used without any problem and covered under Prosense warranty The warranties made...

Page 3: ...onnection 11 4 4 Detector Connections 11 4 5 PPS Series Detectors Connections 13 4 5 Relay Outputs 15 5 FIRST RUN 15 5 1 Automatic Test 16 5 2 LED Test 16 6 PROGRAMMING 16 6 1 Set FAN1 Relay Level 16...

Page 4: ...el exceeded and deacticvated after 240 seconds than the alarm status returned to normal The PPS Panel has one power module that can provide power to all zone modules This power module has also two rel...

Page 5: ...uld not be placed near by high voltage cables or power cable coaxial cables or transmitters welding stations or frequency regulators The PPS Control Panel box produced based on IP66 standard specifica...

Page 6: ...ecommends having cable entries from the lower side Electronic board is located in the front cover of the panel The power supply is located at the back of panel box The power must be connected to this...

Page 7: ...configuration and display the detector details Their functions are given in table The key assignments may vary depending on the menu page Key Function For Configuration Function For Display Operation...

Page 8: ...th key Diagram 7 Locker 3 1 LCD Screen PPS Panel has 2x8 LCD display on each zone module to show detector address measurement level and range as well as detector gas type Sign sample Meaning CO Measur...

Page 9: ...Power module equipped with two relay modules as fault and alarm Fault relay will be activated when any of the detector goes in to fault status and alarm relay will be activated when any of the zone mo...

Page 10: ...onnected to the system Take extra care to use correct poles while connecting the batteries The cables or main board can be damaged in case of mixing pins or making short circuits Backup batteries must...

Page 11: ...ld be done with 1 5mm2 cross section cable The total distance between control panel and detectors should not exceed 800m Detector connections should be made with 4 core cable wire that 2 for power and...

Page 12: ...mmunicate up to 32 detectors In case less then 32 detectors connected control panel would not show non existent detectors Unused detectors should be deactivated on channel settings menu steps The last...

Page 13: ...RS485 board should be done by using connection cable EIA RS485 2 core wires with section 0 22 0 35 mm2 and shielded Nominal capacity between the wires 50pF m and nominal impedance 120 Ohms Detectors w...

Page 14: ...am 15 RS485 Modbus serial communication module end of line jumper Important Only the last detector on the serial bus should have end of line pin 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3...

Page 15: ...elated zone This relay will be deactivated afte 240 seconds when the status returned to normal The relays are configured as NO Normally Open by default at factory The relay configurations cannot be ad...

Page 16: ...and turn off all of them except on LED as it is always blinking 6 PROGRAMMING The panel is already programmed and ready for using when shipped User should adjust the gas type alarm settings for each...

Page 17: ...in menu or press again to exit from menu FAN1 level cannot be adjusted higher than the FAN2 relay level or Alarm relay alarm level Thus user should adjust first the FAN2 level or Alarm level 6 2 Set F...

Page 18: ...ported by PPS Manager which are CO NO2 LPG Once decided press Menu button to continue It will show the current level Alarm level can be increased or decreased via pressing up and down arrow buttons Fo...

Page 19: ...e connected detectors it asks user to confirm gas type The reason is to make sure whether user connected the detector by mistake or real usage as different gas types have different behaviours To set g...

Page 20: ...f gas Once gas type set use T button to return back to main menu or press again to exit from menu 6 6 Set Language PPS Manager currently supports two languages which are English and Turkish User can c...

Page 21: ...ration It will take at least two minutes to complete scan operation The screen will show number of detectors when scan opration completed Press T button to return back to main menu Menu will return to...

Page 22: ...fault relay will be activated any one of the zone module raises a fault condition Same as fault alarm relay will be activated any one of the zone module raises an alarm condition The LEDs and related...

Page 23: ...and fault LED activated Here the code details that can help to understand problem and find a resolution Fault Code Details 10 EFuse Dedektor Power Line Fault 11 No detector installed on zone module 1...

Page 24: ...24 PRS UM PPSM EN Rev 03 10 04 2020 Declaration...

Page 25: ...y fault is not found with he the equipment Prosense Technology shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or oper...

Reviews: