VTrak J830s, J630s Product Manual
52
The system returns:
-------------------------------------------------------------------
Time Since Power Up
: 0 days 0 hours 1 minute 45 seconds
Enclosure
: SBB SAS 6G JBOD 4U-24 Bay
Serial Number
: S987123
I/O Module ID
: 2
Max I/O Module Cnt
: 2
Firmware Version
: 6.00.0000.32
I/O Module Role
: Secondary
•
•
•
Slot 24
No Device Attached
CN#1
50 0E 00 4A 00 BD 22 55
CN#2
50 0E 00 4A 00 BD 22 3F
PSU ID
Shutdown Event
=============================
PSU 01
AC loss
PSU 02
AC loss
Because the new I/O module is installed in the right slot, it automatically
takes ID 2 and the Secondary role under enclosure information.
8.
Disconnect your serial cable from the new I/O module.
Replacing a Power Supply Fan
The power supply fans cool the VTrak enclosure as well as the power supplies
themselves. If a power supply fan fails, replace the fan assembly as soon as
possible. Contact Promise Technical Support for replacement parts. See
page 44.
Warning
The electronic components within the VTrak are sensitive to
damage from Electro-Static Discharge (ESD). Observe
appropriate precautions at all times when handling the VTrak or its
subassemblies.