Tab. 1: Terminal assignment
Name
Terminal identifier
Terminal no.
Pole
Function
Output relay output
1
P1
1
C
Shut the servomotor.
2
NO
3
NC
Output relay output
2
P2
4
C
Open the servomotor.
5
NO
6
NC
Response signal
input
XR
7
-
Feedback servomotor
position.
8
S
9
+
Output relay output (P1, P2):
n
Type of contact: Changeover contact with interference-sup‐
pressed varistors
n
Load capacity: 250 V AC, 3 A max., 700 VA
n
Contact lifespan: > 20 x 10
5
switching operations
Position feedback input: XR
n
Galvanically isolated from the power relay contacts
n
Insulation voltage: 500 V
n
Potentiometer to be connected: 0 Ω ... 1 kΩ
n
Accuracy (without potentiometer errors): 1% of input range
n
Dissolution: 0.5 % of input range
n
Manipulating time: min.: 25 s / max.: 180 s
Electrical data
Wiring diagram
7