Power supply is no problem even for DC12V, WEC200 or Electric Lock.   

Please note

 the 

current is not more than 

3A

 for electric lock particularly.    You may use DC12V right now if your 

survey is available.    Unfortunately, if only DC24V is workable for your electric lock, you are still able 

to use your own electric lock with DC24V separately.    As for model WEC200, it accepts the power 

supply of DC12V only.    Definitely, two GND should be connected together, and then the whole 

system works actually.

 

(Refer to the illustration of this chapter 

– separateness way of power 

supply).

 

 

If your electric lock supports AC, 

please note

 the voltage volume rates at 1A/125VAC for the 

contact of relay, so the current is not more than 

1A

.    Some countries accept 220VAC~240VAC only 

for their local voltage, we hence suggest that you may use an external relay. Let the relay of WEC200 

control your external relay unaffectedly. 

 

Power Supply 

The power supply of WEC200 adopts DC12V.    If only one power supply is available for WEC200 

and electric lock together, moreover current of the electric lock is I

LOCK

 fortuitously, you have to 

adjust 2*I

LOCK

 at least for the power supply.    WEC200 itself is causative, which its consumable 

current stays at 150mA.    The running electric locks on the market exceed in this value widely.    In 

order to prevent the power consumption is incapable load under the status of activation or 

deactivation, supernumerary power supply is necessary, which lose voltage in a second and 

re-activate WEC200 again. 

(If you discover this status is appeared when testing, please use other 

power supply) (Refer to last illustration)   

We strongly suggest to use separate power supply for 

electric lock.

 

 

All above is just mentioning only one electric lock is using.    If using two electric locks, the power 

supply should be loaded by 4*I

LOCK

 at least. 

For the sake of safety, power supply device should be mounted at a safe location. 

 

 

Door Open Sensor 

Two kinds of door open sensor are normally-opened and normally-closed dividedly.    N.C. is rather 

popular on the market, which is proper to connect the terminals of INPUT1 or INPUT2 for WEC200. So 

WEC200 is working the current status for the entrance. 

 

Min. 

Type 

Max. 

V

IH 

(logic1) input 

voltage 

7.5V 

11.2V 

12V 

V

IL 

(logic0) input 

voltage 

0V 

0.8V 

7.3V 

If voltage of INPUT1 contact is 0V

DC, 

please refer 6-C (stated as below).    Logic0 is generated when 

Data access is processing (

as above table

) If >/=7.5VDC or vacant, logic1 is generated. 

Summary of Contents for WEC200

Page 1: ...tion Chapter 3 Installation Chapter 4 Pin Assignment Chapter 5 How to integrate with Access Control Chapter 6 Protocol Chapter 7 Communication Ethernet Module Chapter 8 Specification Appendix A LED2 S...

Page 2: ...Code and Card Code directly If your computer is equipped with one RJ45 port you are able to connect the 10 100BaseT Ethernet and support TCP IP UDP with your Wiegand reader through WEC200 Featuring of...

Page 3: ...0 D1 for connection 4 wire connection is a must have to short distance communication which is good enough but to long distance wiring will be too much trouble We suggest applying 2 WEC200 to serve as...

Page 4: ...hich is fail LED1 Green normally displays the status of the Ethernet Port When receiving an Internet package the LED1 will be cut off temporarily until the package is received entirely 4 C DC JACK Pin...

Page 5: ...closed N C What is N O It means when deactivation is appearing the status for the electric lock is unlock otherwise if activation is appearing for the electric lock the status will be switched to lock...

Page 6: ...least for the power supply WEC200 itself is causative which its consumable current stays at 150mA The running electric locks on the market exceed in this value widely In order to prevent the power co...

Page 7: ...Please refer to the example we illustrate Applying a separate power supply at DC12V output which is good enough to supply the power requirement for both of electric lock and alarm The part of lock is...

Page 8: ...ware Number V Version Y Revision For example STX ROM0722A7 CR 6 B Get service code HOST to DEVICE 4 bytes STX G S CR 02H 47H 53H 0DH DEVICE to HOST 12 bytes STX XXXXXXXXXX CR You can get the unique se...

Page 9: ...o HOST 3 bytes STX X CR You can get the type with this command X 0 receive only 1 transmit only default 6 G Get format status HOST to DEVICE 4 bytes STX G F CR 02H 47H 46H 0DH DEVICE to HOST 3 bytes S...

Page 10: ...s n 255 relay 1 keeping in close status 6 K Set relay2 output status HOST to DEVICE 5 bytes STX S A n CR 02H 53H 41H byte 0DH DEVICE to HOST 3 bytes STX ACK NACK CR You can activate relay2 n 0 1s stat...

Page 11: ...status a string data will go automatically by STX C CR to give you the notice of input is changing due to 0 1 s has detected itself It implied that several messages might send out already After receip...

Page 12: ...band UDP T inband TCP or command phase TCP e error status no errors detected E running in the error mode i IP address status not obtained yet I obtained via DHCP M fixed set manually c data connectio...

Page 13: ...Data _ A0 2 3 5 0 62 192 168 100 216 Note 1 This is a broadcasts command so the remote host IP needs to be set to 255 255 255 255 2 The default password is blank 3 For more details please refer to the...

Page 14: ...k1 RemoteHost 192 168 100 216 Winsock1 SendData PS01 Note 1 For more details please refer to the on line help file of DS Manager tibbo_docs chm on Set I O Pin Status Sx instruction section 7 B Reply C...

Page 15: ...consumption 140mA 12VDC Protocols Communicates with server on the networking using TCP or UDP protocols Indication type Three LEDs display status information One built in buzzer 2 sets of input 2 set...

Page 16: ...nection TCP or UDP with any network host is currently established Sending ARP Displayed when the DS is sending ARP requests to find out the MAC address of the destination network host with which the D...

Page 17: ...S S S C C C C C C C C C C C C C C C C P P E E E E E E E E E E E E O O O O O O O O O O O O P Summed for even parity E Summed for odd parity O Wiegand interface 30 bit format 1 2 3 4 5 6 7 8 9 10 11 12...

Page 18: ...O O O O O O O O O O O P Summed for even parity E Summed for odd parity O Wiegand interface 38 bit format 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35...

Page 19: ...EC200 00 and WEC200 01 To detail this for example if the tag code is FC177ID25111 then for WEC200 00 it will be packaged as Hex 02h 57h 46h 43h 31h 37h 37h 49h 44h 32h 35h 31h 31h 31h 0Dh W F C 1 7 7...

Page 20: ...U program This chapter doesn t open all the commands Only list some of them that customer may use Reboot Description Reboot the WEC200 01 device Command Hex 05h 54h 45h 1Ah T E The command package sta...

Reviews: