REV 1.0 / PL-QCK-WSENSOR/VC2000-EN
14
VAV Zone Controller
(PL-C1000-VAV)
INT Port: Incoming Modbus RS485 communication from digital
sensor
-OR-
Remote computer with Prolon Focus software
Digital Input for night setback / Standby mode
Multi-function analog input
Common for all the inputs
Temperature setpoint (0-10K potentiometer)
Room temperature sensor (10K thermistor)
Output 5 (analog 0-10VDC) (Max Current: 40 mA)
Output 4 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 3 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 2 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 1 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Power source of the controller (24 VAC - Class 2)
NET Port: Incoming Modbus RS485 communication
- OR -
BACnet MS/TP
32-122 °F (0-50 °C) Non-condensing
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN
15
INT Port: Incoming Modbus RS485 communication from digital
sensor
-OR-
Remote computer with Prolon Focus software
Digital Input for night setback / Standby mode
Multi-function analog input
Common for all the inputs
Temperature setpoint (0-10K potentiometer)
Room temperature sensor (10K thermistor)
Output 5 (analog 0-10VDC) (Max Current: 40 mA)
Output 4 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 3 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 2 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Output 1 - Isolated or source, TRIAC 24 VAC
(max current: 300 mA)
Power source of the controller (24 VAC - Class 2)
NET Port: Incoming Modbus RS485 communication
- OR -
BACnet MS/TP
cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1