REV 1.0 / PL-QCK-WSENSOR/VC2000-EN
4
Analog Sensor
(PL-RS)
COM
THERM
COM
POT
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Schedule override
Room temperature
Setpoint (10K)
Dimensions and Wiring
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN
5
COM
THERM
COM
POT
4.96”
(126 mm)
1.30”
(33 mm)
3.23”
(82 mm)
Schedule override
Room temperature
Setpoint (10K)
Temperature table (thermistor: 10K Type 3)
Fahrenheit
41
50
59
68
77
86
95
104
Celsius
5
10
15
20
25
30
35
40
Ohms
25395
19903
15714
12493
10000
8056
6530
5324