Prolon PL-C1000-VAV Quick Start Manual Download Page 1

QUICK START 

GUIDE

VAV CONTROLLERS & WALL SENSORS

www.proloncontrols.com  |   [email protected]

17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9

REV 1.0

PL-QCK-WSENSOR/VC2000-EN

Summary of Contents for PL-C1000-VAV

Page 1: ...QUICK START GUIDE VAV CONTROLLERS WALL SENSORS www proloncontrols com info proloncontrols com 17 510 rue Charles Suite 100 Mirabel QC J7J 1X9 REV 1 0 PL QCK WSENSOR VC2000 EN ...

Page 2: ...pplication or misuse of its products All trademarks are the property of their respective owners REV 1 0 PL QCK WSENSOR VC2000 EN 3 Analog Sensor PL RS 4 Dimensions and Wiring 4 Digital Sensor PL T200 6 Dimensions and Wiring 6 Digital Sensor PL T500 8 Dimensions and Wiring 8 Digital Sensor PL T1000 10 Installation 10 Auxiliary Analog Input 12 Operation 12 Changing the Setpoint 13 Schedule Override ...

Page 3: ...perature Setpoint 10K Dimensions and Wiring REV 1 0 PL QCK WSENSOR VC2000 EN 5 COM THERM COM POT 4 96 126 mm 1 30 33 mm 3 23 82 mm Schedule override Room temperature Setpoint 10K Temperature table thermistor 10K Type 3 Fahrenheit 41 50 59 68 77 86 95 104 Celsius 5 10 15 20 25 30 35 40 Ohms 25395 19903 15714 12493 10000 8056 6530 5324 ...

Page 4: ...26 mm 1 30 33 mm 3 23 82 mm Schedule override hold for 3 second Communication RS485 Power 2 VA max RJ45 connection to C1000 REV 1 0 PL QCK WSENSOR VC2000 EN 7 INT A INT B 24VAC COM 4 96 126 mm 1 30 33 mm 3 23 82 mm Schedule override hold for 3 second Communication RS485 Power 2 VA max RJ45 connection to C1000 ...

Page 5: ...m Communication RS485 Power 2 VA max RJ45 connection to C1000 Schedule override Hold 3 seconds Change unit F C Double click REV 1 0 PL QCK WSENSOR VC2000 EN 9 INT A INT B 24VAC COM 4 96 126 mm 1 30 33 mm 3 23 82 mm Communication RS485 Power 2 VA max RJ45 connection to C1000 Schedule override Hold 3 seconds Change unit F C Double click ...

Page 6: ...s to the terminal blocks and reconnect the terminal blocks See Figure 2 If using CAT5 cable Plug the cable into the RJ45 jack of theT1000 if CAT5 cable is opened at the controller refer to Figure 3 for pinout of the T1000 s RJ45 jack 5 Reconnect top cover IMPORTANT Do not install the thermostat under the following conditions Any location exposed to direct sunlight On an outside wall Near an air di...

Page 7: ...o detect finger proximity There are no moving parts to push or rotate The T1000 is controlled using simple scrolling tapping or holding motions performed around the circle of the touch pad The center of the circle is unused Scroll clockwise or counterclockwise to adjust or navigate Tap here to ENTER Tap here to go BACK 5 6 7 8 9 10 REV 1 0 PL QCK WSENSOR VC2000 EN 13 Changing the Setpoint Schedule...

Page 8: ...Class 2 NET Port Incoming Modbus RS485 communication OR BACnet MS TP 32 122 F 0 50 C Non condensing REV 1 0 PL QCK WSENSOR VC2000 EN 15 INT Port Incoming Modbus RS485 communication from digital sensor OR Remote computer with Prolon Focus software Digital Input for night setback Standby mode Multi function analog input Common for all the inputs Temperature setpoint 0 10K potentiometer Room temperat...

Page 9: ...ng on the flow cross used this translates to roughly 0 3500 ft min 32 122 F 0 50 C Non condensing REV 1 0 PL QCK WSENSOR VC2000 EN 17 Service pin General purpose analog input 0 5 VDC 4 20mA 10K thermistor Supply Radiant Zone Occupancy Discharge Digital sensor T1000 T500 or T200 Remote computer with Focus Analog output 0 10 VDC max current 40 mA Network communication Digital output Isolated Triac D...

Page 10: ...s with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Industry Canada This Class B digital apparatus meets all the requirements of the Canadian Interference Causing Equipment regulations Cet appareil numéri...