5. Connection and Operation
5.1 Connection and operation
1) Inspection:
Inspect the packaging carton and its contents for damage. Please
inform the transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use.
Note: Please ensure that the incoming feeder is isolated and secured to
prevent it from being switched back on again.
2) Connection:
2.1) UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket with
protection against electric current, and pay attention to the capacity of the
socket: over 10A for UPS T1000(S) & UPS T2000, over 16A for UPS
T2000S& UPS T3000(S).
2.2) UPS Output Connection
The output of UPS T1000(S) and UPS T2000S(Non CE) are socket-types
only. Simply plug the load power cord to the output sockets to complete
connection.
Model No.
Output Socket (pcs)
Terminal Block
UPS
T1000/1000S
4
Nil
UPS T2000
6
Nil
UPS T2000S
4(CE) 6(Non CE)
Available(CE) Nil (Non CE)
UPS
T3000/3000S
4(CE) 3(Non CE)
Available
Besides output sockets, UPS T2000S(CE) and UPS T3000/3000S has the
terminal block available for output as well. The wiring configuration is
shown as the following procedure:
a) Remove the small cover of the terminal block
b) Use AWG14 or 2.1mm2 wires for wiring configuration
The system may be installed and wired only by qualified electricians in
accordance with applicable safety regulations!
When installing the electrical wiring, please note the nominal amperage
of your incoming feeder