-16-
5.7 Audible alarm mute function:
If the alarm is too annoying in battery mode, you may press “I” button
continuously for more than 1 second to clear it. Moreover, the alarm
will be enabled when the battery is low to remind you to shutdown the
load soon.
If the alarm is too annoying in bypass mode, you may press “ “button
continuously for more than 1 second to clear it. The action doesn’t
affect the warning and fault alarm.
5.8 Operation procedure of external battery for long backup
time model (“S” model)
(1) Use the battery pack with voltage: 36VDC for I1000S (3 pcs of
12V batteries), 96VDC for I2000S/I3000S (8 pcs of 12V batteries).
Connection of batteries more than or less than required will cause
abnormality or permanent damage.
(2) One hard wiring type battery terminal on the rear panel is used for
connecting the battery pack.
(3) The battery connection procedure is very important. Any
incompliance may result in the risk of electric shock. Therefore,
the following steps must be strictly complied with.
(4) Make sure the mains input is cut off, if there is a battery breaker
then turn it off first.
(5) Remove the small cover of terminal block, prepare the battery
cable which should be able to carry the current of >30A for
1KVA, >22A for 2KVA, >33A for 3KVA, the cross section area
should be great than 4
mm
2
for all model. And battery wire color is
recommended as following:
+
+
+
+
GND
-
-
-
-
Red wire
Green/Yellow wire
Black wire
Summary of Contents for UPS I1000
Page 1: ...USER MANUAL ONLINE UPS UPS I1000 2000 3000 Uninterruptible Power Supply www pinnacle co za...
Page 36: ...33 DB 9 Interface of AS400 communication protocol...
Page 38: ...35 Appendix Rear panel Back View of I1000 Back View of I1000S...
Page 39: ...36 Back View of I2000 Back View of I2000S...
Page 40: ...37 Back View of I3000 Back View of I3000S...
Page 41: ...38 614 09358 00...