Progressive Dynamics PD52 Series Installation And Operation Manual Download Page 3

Consult a licensed electrician or RV technician for installation assistance 

 

GENERAL OPERATION

 

 

 

When power is applied to the shore side, the contactor activates and supplies power to the panel - GREEN shore LED on 
front panel will light. 

 

When power is applied to the Gen side there is a 20-45 second delay then the Gen side contact will activate, power will go to 
the panel from the Gen side and the shore side will be locked out - GREEN generator LED on front panel will light. 

 

If shore power returns while the Gen power is present, nothing will happen. When the Gen power is removed the contactor 
will drop out and allow the shore side to supply power. 

 

In a single leg application, the HOT1 side must be used for the control circuitry to work. For models with surge protection, 
both HOT1 and HOT2 must have power applied for proper operation. 

 

 

HOW TO DISABLE GENERATOR TIME DELAY: 

 

  

 

 

 

 
 
 
 

 

 

PD52DCSD REMOTE DISPLAY 

PD52/53 CONTROL BOARD 

To 

DISABLE

 the time-out function of the 

control board, 

INSTALL

 a .100” jumper of 

the connector at 

J1

PD52DCS CONTROL BOARD 

To 

DISABLE

 the time-out function of the 

control board, 

REMOVE

 the jumper 

installed on the connector at 

J1

The PD52DCSD remote display is equipped with three LED lights. The 
GREEN LEDs indicate SHORE power or GENERATOR power.  The RED 
LED indicates an error has occurred and the surge protection may no longer 
be functioning. 
 
If the RED LED is illuminated, please contact Progressive Dynamics service 
department for a replacement control board.  The transfer switch may 
continue to function safely without surge protection. 

Summary of Contents for PD52 Series

Page 1: ...AVINGS LOSS OF USE OF ENJOYMENT OR OTHER INCIDENTAL DAMAGES ARISING OUT OF THE USE OF OR INABILITY TO USE THE PRODUCT THIS INCLUDES DAMAGES TO PROPERTY AND TO THE EXTENT PERMITTED BY LAW DAMAGES FOR PERSONAL INJURY THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IV PROOF OF PURCHASE A warranty claim must be accom...

Page 2: ...RE NOT DESIGNED FOR USE WITH 240 VOLT SINGLE LEG SUPPLIES APPLICATION OF VOLTAGES IN EXCESS OF 130 VOLTS FROM HOT TO NEUTRAL MAY CAUSE PERMANENT DAMAGE TO THE UNIT The 5200 5300 Automatic Transfer Switches can be installed as shown in figures 1 and 2 provided there is room to route the shore power generator and distribution connection wires The 5200 5300 Automatic Transfer Switches including the R...

Page 3: ...he HOT1 side must be used for the control circuitry to work For models with surge protection both HOT1 and HOT2 must have power applied for proper operation HOW TO DISABLE GENERATOR TIME DELAY PD52DCSD REMOTE DISPLAY PD52 53 CONTROL BOARD To DISABLE the time out function of the control board INSTALL a 100 jumper of the connector at J1 PD52DCS CONTROL BOARD To DISABLE the time out function of the c...

Page 4: ...ING GUIDE PROBLEM POSSIBLE CAUSES ACTION No Output when Plugged into Shore Power Wiring error between shore power and the transfer switch Correct wiring Defective transfer switch Replace transfer switch Wiring error between generator and the transfer switch Correct wiring Generator malfunction Have generator serviced No Output when Generator is Running Wiring error between generator and the transf...