Profort multiGuard DIN4 Quick Manual Download Page 7

 

 

MAKRO 

 

 
 

 

www.profort.com  

Pg. 

7

 

 
Power supply 

12-24V AC/DC min 0,5 A (acquisition) 
NB! Supply must not come into contact with the ground. 

Battery 

3,6V rechargeable Li-ion-battery (acquisition) 

Usage 

Approx. 50 mA when resting (supplied with 12-24 VAC/DC) 
Approx 15 mA when resting (supplied with battery) 
150 mA when battery-charged 
2 mA when resting (instruction ‘DN’) and supplied with battery 

Output 

Max. 6 A at 230V AC 
Max. 6 A at 35V DC 

Inputs, digital

 

Max. 1V, 2 mA (GND) 

Input 0: also connect/disconnect (level/pulse) 

Min. 18V max 30 V (24V DC) 

Input 1: also pulse/minute counter 

 

Input 2: also pulse counter 

Input, analog 

0

-10V DC  

0/4-20mA 
PT-100 
Profort temperature sensor (Profort-no. 007995) 

Pulse- and minute counter

 

Max. 10Hz. Maks. one mio. pulse or minutes 

Dimension 

4 DIN-modules 
69x86x57 mm, weight: 125 g. 

Temperature 

– 20 °C - +55 °C 

Antenna 

1 internal antenna for GSM-modem.  
Possibility of adding external antenna (Profort-no. 369003) with 2,5 m cable and 5 m extension (Profort no. 
301110) or 10 m extension (Profort no. 301111) 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for multiGuard DIN4

Page 1: ...e 12 24 VAC DC and if necessary a rechargeable 3 6 V Li ion battery 3 Turn on the power A red diode is lit After max 1 min the diode flashes approx every 2 sec and the unit is ready The GSM unit inter...

Page 2: ...t com Set up via masterView 1 Open a browser on your PC tablet or smartphone 2 Type http setup masterview dk in the address bar and choose setup or login via www profort dk Log on to the portal or cre...

Page 3: ...spaces 25 in all N2 N9 NA 10 NB 11 NP 25 Delete 1234 N1 Deletes receiver in space no 1 Text on input Add 1234 A0 OPEN TEXT TEXT on input 0 by open break x A0 A2 1234 L0 CLOSE TEXT TEXT on input 0 by c...

Page 4: ...and B0 B zero Deactivate output in case of alarm 1234 G0 Output is not activated on alarm 1234 space G null Add macro 0 to return temperature 1234 M0 TEMP V1 R The unit returns value for analog 1 e g...

Page 5: ...centage 25 is least acceptable value yy battery status 1234 V1 R Downloads measurements on the analog input Connection to the Internet 1234 EA 12345678 12345678 GPRS traffic starts 12345678 mobile num...

Page 6: ...ble to set up 20 macros Set up macro with command 1234 M1 NAME COMMAND Sets up macro 1 M0 M9 and R0 R9 under the name NAME and adds command in More commands in the same macro can be separated by semic...

Page 7: ...230V AC Max 6 A at 35V DC Inputs digital Max 1V 2 mA GND Input 0 also connect disconnect level pulse Min 18V max 30 V 24V DC Input 1 also pulse minute counter Input 2 also pulse counter Input analog...

Page 8: ...receiver 230V 12 24V power supply 9V rechargeable back up battery acquisition Modbus interface IP 65 box Touch display for set up and programming multiGuard Remote IO 1 relay output 2 senders of infra...