PROFIBUS-DP RS485 Installation / Pre-commissioning
TR-Electronic GmbH 2011, All Rights Reserved
Printed in the Federal Republic of Germany
Page 86 of 131
TR - ECE - BA - DGB - 0089 - 01
10/24/2011
The real address assignment is performed by means of menu
PLC
-->
PROFIBUS
-->
Assign PROFIBUS Address…
Now, in the input window
Assign PROFIBUS Address
the new address can be
assigned, the address range includes the addresses 1 to 99. By means of button
OK
the new address is stored permanently in the non volatile memory of the
measuring system without feedback. This procedure must be finished with
POWER OFF/ON.
For checking purposes, whether the new address was set, menu
PLC
-->
Display Accessible Nodes
should be executed. Hereby the address
assignment is finished.